* Total system load is limited by the
available PSU output. The NOTIFIER
Loop and Battery Calculator Support
Tool should be used to ensure that the
system is NOT overloaded.
997-433-000-5, Issue 5
May 2010
ID2000 Series Installation & Commissioning Manual
Sounder Output Rating
Type:
Output voltage:
Maximum load:
Fuse rating
Monitoring:
Volt-free Contact (VFC) Output Rating
Type:
Maximum load:
Fuse rating:
24 Volt DC Auxiliary Output Rating
Output voltage range:
Maximum load:
Quiescent:
Alarm:
Fuse rating:
Note: It is recommended that the auxiliary ouput should not
Loop Outputs (Two Standard and Two Optional)
Output voltage:
Maximum load:
Loop driver source
impedance:
Up to 198 loop devices (up to 99 sensors and 99 modules) may
be fitted to each analogue loop. For system limitations refer to
Section 4, Sensors and Modules.
The communication with devices on the loop uses the
NOTIFIER 'CLIP' protocol. Refer to Appendix 3 for a list of
compatible devices and loading limitations.
RS232 Serial Port (Optional)
Isolation:
Baud rate:
Connector:
Max cable length:
RS485 Serial Port (Optional)
Isolation:
Baud rate:
Connector:
Maximum cable length: 3000m (minimum of 1mm
A2 - 4
Voltage reversal
26 to 28V when active;
-6.8V to -9V when inactive
1A *
T 1A 250V
Open- and short-circuit
Single pole change-over
Contacts rated 30V 1A
Not fused
26 to 28 V
150mA *
1A *
T 1A 250V
be used in the quiescent state other than to provide a
supply to drive ancillary devices' power indicators.
22.5 to 26.4V
0.5A*
3.8 ohms at 22.5V
Functional at 30V.
Software-selectable up to 9600
Baud.
Terminal block on RS232 PCB.
15m
Functional at 30V.
1200 Baud.
Terminal block on RS485 PCB.
screened cable recommended)
2