MODUPLUS® TRADELINE
Mounting Moduplus® Tradeline on gas valve. (see fig 3)
• Verify that all parts are present in Moduplus® tradeline
box (1 moduplus®, 1 gasket, 2 screws, 1 cap)
• Shut off gas and power supply, disconnect Moduplus® coil
wiring and disconnect pressure feedback connection (if
applicable)
• Remove old Moduplus® regulator and discard gasket.
Place new gasket at the bottom side of Moduplus®.
Orientation of the gasket must be as indicated in figure 3!
Push gasket over the small bosses (A), so that the bosses
show fully through the gasket.
• Mount Moduplus® on the gas valves.
The electrical connectors of the Moduplus® coil must face
the coil of the gas valve. (see fig. 2)
The 2 mounting screws must be fastened to 3 Nm.
• Switch on gas and power supply, energize operator of gas
valve. Check for outerwall leakage around perimeter of
Moduplus®.
• Adjust maximum and minimum pressure setting according
chapter 'Adjustment, Checkout and Maintanance'
• Place cap over adjustment screws until it snaps over
protruding circular boss and reconnect pressure feedback
connection (if applicable)
Manufactered for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce 16, 1180 Rolle, Switzerland by its Autorized Representative:
Automation and Control Solutions
Combustion Controls EMEA
Honeywell BV
Phileas Foggstraat 7
7821 AJ Emmen
The Netherlands
Tel.: +31 (-)591 695911
Fax: +31 (-) 591 695200
http://ecc.emea.honeywell.com
EN1R-9175 0908RA-NE
Fig. 3. Moduplus® Tradeline parts