Commissioning
4.6 Basic parameterization of the drive objects
Connecting signal sources
1. Connect the signal source for the "Infeed operation" (p0864) command.
2. Interconnect the signal source for command "OFF1 (low active)" (p0840).
This command corresponds to control word 1 bit 1 (STW1.1) in the PROFIdrive profile.
3. Interconnect the 1st signal source for command "OFF2 (low active) signal source 1 "
(p0844).
This command corresponds to control word 1 bit 1 (STW1.1) in the PROFIdrive profile.
4. Interconnect the 2nd signal source for command "OFF2 (low active) signal source 2 "
(p0845).
5. Interconnect the 1st signal source for the "No quick stop/quick stop (OFF3) signal source
1" command (p0848).
This command corresponds to control word 1 bit 2 (STW1.2) in the PROFIdrive profile.
6. Interconnect the 2nd signal source for the "No quick stop/quick stop (OFF3) signal source
2" command (p0849).
This command corresponds to control word 1 bit 2 (STW1.2) in the PROFIdrive profile.
7. Interconnect the signal source for the "Enable operation" command (p0852).
This command corresponds to control word 1 bit 3 (STW1.3) in the PROFIdrive profile.
126
Commissioning Manual, (IH3), 07/2016, 6SL3097-4AA10-0BP0