Air-to-Water Heat Pump Systems PAW-VP1000LDHW PAW-VP750LDHW PAW-VP500LDHW PAW-VP200LDHW PAW-VP380L Domestic Hot Water System for R410A and R32 Use Technical Manual Commercial System Air Conditioner 20191101-1...
Important Information regarding the Refrigerant Used............Check of Density Limit ......................Technical Data of Indoor Unit ................1.1 Indoor/outdoor unit specifications ..................1.1.1 Tank model PAW-VP1000LDHW ................1.1.2 Tank model PAW-VP750LDHW .................. 1.1.3 Tank model PAW-VP1000/750LDHW ................. 1.1.4 Tank model PAW-VP500LDHW .................. 1.1.5 Tank model PAW-VP200LDHW ..................
Page 6
Contents System drawings ....................System PAC DHW ....................... System PACi/ECOi DHW ..................... System PAC DHW with buffer tank ..................System U-16MF3E8 ......................System U-16MF3E8 with DHW ................... System PACi PAW-VP380L ....................System PACi and PAW-VP 380L Cooling/Heating ............Electrical Wiring ....................General precautions on wiring ..................
Page 7
Contents Error Codes PACi & ECOi ................... Check Before Requiring Services ..............11.1 Factory pre-installed Back-up heater ................11.2 Electrical connection check points ................... Legionella Protection Control ................Booster Heater for PAW-VP380L ................ 13.1 Installation of the heating unit ................... 13.2 Electrical connection ......................
The operation of the products can also be carried out by private persons. Treated products This manual covers the following products: R32 and R410A products ● Indoor Units, and connectable outdoor units combinations Indoor Unit Type DHW tank PAW-VP1000LDHW PAW-VP750LDHW PAW-VP500LDHW PAW-VP200LDHW Buffer tank — — PAW-VP380L —...
Page 9
Introduction Used symbols The text in this manual uses various notices, symbols and textual representations, which are briefly explained below. Safety-related cautions Safety-related information alerts users to hazards and provides instructions for the safe, desig- nated use of the product. This guide uses the following warnings and signs: DANGER This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
Page 10
Introduction Further notes Important Important notes that must be followed to ensure that the units work as intended. Note Hints for more useful information. Text displays Indicates instructions in a warning. ► 1., 2., 3..or a, b, c ... Indicate steps to be performed in the specified order.
Safety Instructions Safety Instructions This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. For safe installation and trouble-free operation, you must: ●...
Safety Instructions Special Precautions DANGER When Wiring Electrical shock can cause severe personal injury or death. Only a qualified, experienced electrician should attempt to wire this system. ● Do not supply power to the unit until all wiring and tubing are completed or recon- nected and checked.
Page 13
Safety Instructions DANGER ► Keep the fire alarm and the air outlet at least 1.5 m away from the unit. In moist or uneven locations Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit.
Page 14
Safety Instructions When Connecting Refrigerant Tubing DANGER ● When performing piping work, do not mix air except for specified refrigerant (R410A or R32, depending on the outdoor unit model) in refrigeration cycle. It causes capacity down, and risk of explosion and injury due to high tension inside the refrigerant cycle.
Page 15
Safety Instructions When Servicing ● Contact the sales dealer or service dealer for a repair. ● Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring. ● Keep your fingers and clothing away from any moving parts. ●...
Safety Instructions Important Information regarding the Refrigerant Used Used refrigerant This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere. Refrigerant type: R410A Refrigerant type: R32 GWP(1) value: 1975 GWP(1) value: 675 (1)GWP = global warming potential (1)GWP = global warming potential Periodical inspections for refrigerant leaks may be required depending on European or local...
Safety Instructions Check of Density Limit U-100PZH2E5 The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the requirements for installation space of appliance are determined according to the refrigerant charge amount [mc] used in the appliance. The minimum indoor floor space compared with the amount of refrigerant is roughly as follows, in case it is installed in a living area: PAW-VP200LDHW, PAW-VP500LDHW must be calculated as wall mounted.
Page 18
Safety Instructions U-200PZH2E8 U-250PZH2E8 PAW-VP750LDHW, PAW-VP1000LDHW must be calculated as floor mounted. PAW-VP380L must be calculated as wall mounted. Floor mounted 7.80 kg Max. charge for outdoor model U-200PZH2E8 R32 max. U-250PZH2E8 allowable charge for occupied space Wall mounted [kg] For R410A please refer to installation manual for outdoor unit.
Technical Data of Indoor Unit Technical Data of Indoor Unit Indoor/outdoor unit specifications 1.1.1 Tank model PAW-VP1000LDHW Heat Pump Model U-250PZH2E8 Tank Model PAW-VP1000LDHW Volume Height×Diameter 2210x990 Connections to the water supply network RP 1 1/4” Net weight / with water...
Technical Data of Indoor Unit 1.1.2 Tank model PAW-VP750LDHW Heat Pump Model U-250PZH2E8 Tank Model PAW-VP750LDHW Volume Height×Diameter 1855x990 Connections to the water supply network RP 1 1/4” Net weight / with water 179 / 929 Heat Pump Nominal electrical power 7.14 Reference tapping cycle Energy consumption by chosen cycle A7/W10-55...
Technical Data of Indoor Unit 1.1.3 Tank model PAW-VP1000/750LDHW Heat Pump Model U-16MF3E8 U-16MF3E8 Tank Model PAW-VP1000LDHW PAW-VP750LDHW Volume Height×Diameter 2210x990 1855x990 Connections to the water supply network RP 1 1/4” RP 1 1/4” Net weight / with water 191 / 1121...
Technical Data of Indoor Unit 1.1.4 Tank model PAW-VP500LDHW Heat Pump Model U-100PZH2E8 Tank Model PAW-VP500LDHW Volume Height×Diameter 1660x790 Connections to the water supply network RP 3/4" / 1" Net weight / with water 122 / 632 Heat Pump Nominal electrical power 2.32 Reference tapping cycle Energy consumption by chosen cycle A7/W10-55...
Technical Data of Indoor Unit 1.1.5 Tank model PAW-VP200LDHW Heat Pump Model U-100PZH2E8 Tank Model PAW-VP200LDHW Volume Height×Diameter 1568×590 Connections to the water supply network RP 3/4" / 1" Net weight / with water 54 / 254 Heat Pump Nominal electrical power 1.30 Reference tapping cycle Energy consumption by chosen cycle A7/W10-55...
Technical Data of Indoor Unit 1.1.6 Tank model PAW-VP380L Heat Pump Model U-200PZH2E8 Tank Model PAW-VP380L Cooling capacity at 35°C, water outlet 7°C 12.80 Heating capacity 25.00 Heating capacity at +7°C, heating water temperature at 40/45°C 23.00 COP at +7°C, with heating water temperature at 40/45°C 3.26 Heating Energy Efficiency class at 35°C ηsh (LOT1)
Technical Data of Indoor Unit Outlines and dimensions 1.2.1 Tank model PAW-VP1000LDHW R 2460 2210 1846 1/2” 1475 1 1/4” 1275 Rp 1 1/4” All dimensions in mm. Note R value indicates maximum overturning height. PAW-VP•LDHW - Technical Manual – 2019-11...
Technical Data of Indoor Unit 1.2.2 Tank model PAW-VP750LDHW R 2090 1855 1426 1/2” 1305 1 1/4” 1085 Rp 1 1/4” All dimensions in mm. Note R value indicates maximum overturning height. PAW-VP•LDHW - Technical Manual – 2019-11...
Technical Data of Indoor Unit 1.2.3 Tank model PAW-VP500LDHW R 1840 1660 1380 1100 Rp 3/4” All dimensions in mm. Note R value indicates maximum overturning height. PAW-VP•LDHW - Technical Manual – 2019-11...
Technical Data of Indoor Unit 1.2.4 Tank model PAW-VP200LDHW R 1668 1568 1100 Rp 3/4” All dimensions in mm. Note R value indicates maximum overturning height. PAW-VP•LDHW - Technical Manual – 2019-11...
Technical Data of Indoor Unit 1.2.5 Tank model PAW-VP380L R = 1900 7/8” 1/2” 1820 All dimensions in mm. Note R value indicates maximum overturning height. PAW-VP•LDHW - Technical Manual – 2019-11...
Technical Data of Indoor Unit 1.2.6 PAW-VP-RTC5B-PAC / PAW-VP-RTC5B-ECO 5-5×9 360/359 93,5 All dimensions in mm. PAW-VP•LDHW - Technical Manual – 2019-11...
Important Peak Cut Settings Important Peak Cut Settings Setting of peak cut for all DHW applications 2.1.1 Creation of a peak cut schedule by using the remote controller Time zone to reduce the operation capacity Large Operation capacity Small Proceed as follows Display the menu screen ●...
Page 37
Important Peak Cut Settings Set [Select enable/disable] to [R] M N R O P Select [Set schedule]. M N R Change the setting. Select the field to register. M N R Set the start time and end time. M N R P R M N R (Repeat) Select the operation capacity.
Capacity Performance Data with peak cut 70 % set point TA 46°C U-250PZH2E8/ PAW-VP1000LDHW ● Capacity U-250PZH2E8/PAW-VP1000LDHW at +7°C ambient temperature, heating water from +10°C to 55°C Capacity Performance Data with peak cut demand 70 %/14 kW, heating up time 173 min ●...
Important Peak Cut Settings DHW set temperature 67°C Set point 53°C Δt 5.5°C 55°C Set point Low part tank Middle part tank Upper part tank Mixing temperature 48 °C 50 °C 57 °C 52 °C 52 °C 54 °C 60 °C 56 °C 55 °C 57 °C...
Performance Characteristic Tables Performance Characteristic Tables Capacity table PAW-VP1000LDHW (10 °C) City water inlet temp: 10 °C Outdoor unit type: U-250PZH2E8 Tank type: PAW-VP1000LDHW Ambient Water temp Time Heating Capacity Power Input temperature Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C...
Performance Characteristic Tables Capacity table PAW-VP1000LDHW (12 °C) 12 °C City water inlet temp: Outdoor unit type: U-250PZH2E8 Tank type: PAW-VP1000LDHW Ambient Heating Water temp Time Power Input temperature Capacity Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:38:55 36084.34...
Performance Characteristic Tables Capacity table PAW-VP1000LDHW (15 °C) 15 °C City water inlet temp: Outdoor unit type: U-250PZH2E8 Tank type: PAW-VP1000LDHW Ambient Heating Water temp Time Power Input temperature Capacity Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:30:48 32815.53...
Performance Characteristic Tables Capacity table PAW-VP1000LDHW (18 °C) 18 °C City water inlet temp: Outdoor unit type: U-250PZH2E8 Tank type: PAW-VP1000LDHW Ambient Heating Water temp Time Power Input temperature Capacity Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:26:11 29593.81...
Performance Characteristic Tables Capacity table PAW-VP750LDHW (10 °C) 10 °C City water inlet temp: Outdoor unit type: U-250PZH2E8 Tank type: PAW-VP750LDHW Ambient Water temp Time Heating Capacity Power Input temperature Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:37:15 29687.43 10456.67 2.84...
Performance Characteristic Tables Capacity table PAW-VP750LDHW (12 °C) 12 °C City water inlet temp: Outdoor unit type: U-250PZH2E8 Tank type: PAW-VP750LDHW Ambient Water temp Time Heating Capacity Power Input temperature Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:30:43 27995.43 10022.22 2.79...
Performance Characteristic Tables Capacity table PAW-VP750LDHW (15 °C) 15 °C City water inlet temp: Outdoor unit type: U-250PZH2E8 Tank type: PAW-VP750LDHW Ambient Water temp Time Heating Capacity Power Input temperature Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:23:05 25459.38 9514.76 2.68...
Performance Characteristic Tables Capacity table PAW-VP750LDHW (18 °C) 18 °C City water inlet temp: Outdoor unit type: U-250PZH2E8 Tank type: PAW-VP750LDHW Ambient Heating Water temp Time Power Input temperature Capacity Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:18:45 22959.86 9227.01 2.49...
Performance Characteristic Tables Capacity table PAW-VP500LDHW (10 °C) 10 °C City water inlet temp: Outdoor unit type: U-100PZH2E5/8 Tank type: PAW-VP500LDHW Ambient Water temp Time Heating Capacity Power Input temperature Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:42:39 20931.40 5421.88 3.86...
Performance Characteristic Tables 3.10 Capacity table PAW-VP500LDHW (12 °C) 12 °C City water inlet temp: Outdoor unit type: U-100PZH2E5/8 Tank type: PAW-VP500LDHW Ambient Water temp Time Heating Capacity Power Input temperature Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:35:54 19735.44 5196.61...
Performance Characteristic Tables 3.11 Capacity table PAW-VP500LDHW (15 °C) 15 °C City water inlet temp: Outdoor unit type: U-100PZH2E5/8 Tank type: PAW-VP500LDHW Ambient Water temp Time Heating Capacity Power Input temperature Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:28:00 17950.37 4933.49...
Performance Characteristic Tables 3.12 Capacity table PAW-VP500LDHW (18 °C) 18 °C City water inlet temp: Outdoor unit type: U-100PZH2E5/8 Tank type: PAW-VP500LDHW Ambient Heating Water temp Time Power Input temperature Capacity Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 2:23:32 16188.06 4784.29...
Performance Characteristic Tables 3.13 Capacity table PAW-VP200LDHW (10 °C) 10 °C City water inlet temp: Outdoor unit type: U-100PZH2E5/8 Tank type: PAW-VP200LDHW Ambient Heating Water temp Time Power Input temperature Capacity Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 1:42:59 8748.67 2917.90...
Performance Characteristic Tables 3.14 Capacity table PAW-VP200LDHW (12 °C) 12 °C City water inlet temp: Outdoor unit type: U-100PZH2E5/8 Tank type: PAW-VP200LDHW Ambient Heating Water temp Time Power Input temperature Capacity Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 1:38:42 8250.05 2796.67...
Performance Characteristic Tables 3.15 Capacity table PAW-VP200LDHW (15 °C) 15 °C City water inlet temp: Outdoor unit type: U-100PZH2E5/8 Tank type: PAW-VP200LDHW Ambient Heating Water temp Time Power Input temperature Capacity Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 1:33:42 7502.70 2655.06...
Performance Characteristic Tables 3.16 Capacity table PAW-VP200LDHW (18 °C) 18 °C City water inlet temp: Outdoor unit type: U-100PZH2E5/8 Tank type: PAW-VP200LDHW Ambient Heating Water temp Time Power Input temperature Capacity Set temp [h:m:s] [Ws] [Ws] [Ws / Ws] 45°C 1:30:52 6766.11 2574.77...
Water Piping Installation Water Piping Installation General notes ● Please request a licensed technician to install this water circuit. ● This water circuit must comply with all relevant European and national regulations, i.e. IEC/EN 61770 European Council Directive 98/83 EC. ●...
Water Piping Installation DHW tank unit installation space The DHW tank must be within the following maintenance space. 350 mm or more 400 mm 100 mm or more or more CAUTION ► The tank level must be adjusted before the piping installation can start. Use the three adjustable feet that are located under the floor tank.
Water Piping Installation Filling procedure ● DO NOT turn on any heat source connected to the storage tank until filling it. ● Ensure that all installation requirements, electrical and safety, have been met. ● Check all plumbing and electrical connections are properly connected. ●...
Water Piping Installation Warranty conditions The manufacturer grants a warranty only for defects in material and workmanship on the boilers of its production under normal installation, use and maintenance of the product claimed. The warranty is void if failure to respect the installation specifications listed above under “RULES OF INSTALLATION AND MAINTENANCE”.
Tubing Data and Refrigerant Tubing Data and Refrigerant Tubing data for DHW and outdoor unit combination PAW-VP1000LDHW Combined with outdoor unit U-250PZH2E8 Tubing data [mm (in.)] Liquid tube 1/2” Tubing size outer diameter [mm (in.)] Gas tube 1 1/8” Limit of tubing length (L)
Page 79
Tubing Data and Refrigerant PAW-VP750LDHW Combined with outdoor unit U-250PZH2E8 Tubing data Liquid tube [mm (in.)] 1/2” Tubing size outer diameter [mm (in.)] Gas tube 1 1/8” Limit of tubing length (L) Outdoor unit is placed higher Height differential of Indoor/ Outdoor units (H1) Outdoor unit is placed lower Attention: follow instruction...
Page 80
Tubing Data and Refrigerant PAW-VP500LDHW Combined with outdoor unit U-100PZH2E8 Tubing data Liquid tube [mm (in.)] 3/8” Tubing size outer diameter [mm (in.)] Gas tube 5/8” Limit of tubing length (L) Outdoor unit is placed higher Height differential of Indoor/ Outdoor units (H1) Outdoor unit is placed lower Attention: follow instruction...
Calculation of the refrigerant charge How to calculate refrigerant charge Example 1: Example 2: PAW-VP1000LDHW and U-250PZH2E8 PAW-VP750LDHW and U-250PZH2E8 Tubing lengths L = 25 m Sample tubing lengths L = 10 m (7.5 m – 25 m = 17.5 m) (7.5 m –...
System drawings System drawings System PAC DHW Standard system 1:1 without circulation Outdoor unit City Water in DHW tank Standard system 1:1 with circulation pipe Outdoor unit Qmin = 1 litre/minute Water pump operation schedule At night 15 min OFF 80 min Through the day ON 15 min...
System drawings System PACi/ECOi DHW Standard system with circulation pipe and temperature control system Ø15 mm max. City Water in (Field supplied) accessories 1. Pressure control valve if inlet city water 5. Safety valve 6 or 9.5 bar (field supplied) is more than 6 bar (field supplied) 6.
System drawings System PAC DHW with buffer tank Refer to the next chapter for details. System 1:1 with buffer tank with circulation pipe and charging pump Temperature control valve Qmin = 1 litre/minute Water pump operation schedule At night 15 min OFF 80 min Through the day ON...
Do not use Armaflex insulation. Recommended insulation: Glass wool pipe insulation with aluminum folio with a minimum thick- ness of 20 mm. The solenoid valve kit is delivered for following DHW tanks: PAW-VP-VALV-280 PAW-VP1000LDHW PAW-VP750LDHW PAW-VP•LDHW - Technical Manual – 2019-11...
System drawings System U-16MF3E8 with DHW Mixed System with DHW tank and indoor units, with circulation pipe and temperature control system Ø15 mm City Water in (Field supplied) accessories 1. Pressure control valve if inlet city water is 7. Water pipe inlet/outlet VP1000L/750 more then 6 bar (field supplied) (35 mm) VP500L/200 (22 mm) 2.
System drawings System PACi PAW-VP380L Room heating (and cooling) system with multiple outdoor units and 380L tanks, controlled via outdoor unit U-250 Radiator This system solution has no limitations on capacity or functionality. To increase capacity, in- crease the number of PAW-VP380L tanks. The system solution can be used for heating and cooling.
System drawings System PACi and PAW-VP 380L Cooling/Heating L Room heating (and cooling) system with multiple outdoor units and 380L tanks (Field supplied) accessories 1. Expansion tank (field supplied) 6. TA sensor 2. Water pipe return/turn tank 35 mm (field 7.
Electrical Wiring Electrical Wiring General precautions on wiring 1. Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. 2. Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line.
Electrical Wiring Recommended wire diameter Power supply wiring (B) Power supply cable control box Minimum power supply Circuit breaker Model name Power supply cables L1, L2 (minimum capacity) RTC5B Single phase 220/230/240 V 0.75 mm Power supply cable backup heater Minimum power supply Circuit breaker Model name...
Page 91
Electrical Wiring Wiring system diagram Single-phase model connections RTC5B Power supply Outdoor unit (1-phase) INV unit 220–240 V~, Power supply 50/60 Hz 220–240 V~, Ground 50/60 Hz Ground Ground Remote controller Shielded wire Ground Ground This equipment must be properly earthed. 1.
Electrical Wiring Indoor unit electric wiring diagrams 7.3.1 Wiring system diagram for EX valve magnetic coil PAW-VP•LDHW - Technical Manual – 2019-11...
Electrical Wiring How to connect electrical wires and sensors 7.4.1 How to connect wiring to the terminal Proceed as follows: 1. A screwdriver is inserted with a rocking motion to the stop. 2. The screwdriver is captivated, holding the CAGE CLAMP open, while the wire is inserted.
Electrical Wiring 7.4.2 How to connect temp sensors TA, E1, E2, E3 to the tank system Terminal PAW-VP-RTC5B-PACi Note Remember that the E2 sensor is required. Important When using RTC5B PACi together with DHW tank remove jumper for E2-E2 and connect the sensor E2. ...
Electrical Wiring 7.4.4 How to use with Terminal PAW-VP-RTC5B-PAC E1 E2 PAW-VP-RTC5B-PAC PAW-VP-RTC5B-PAC E1 E2 PAW-VP1000LDHW PAW-VP380L PAW-VP750LDHW PAW-VP500LDHW PAW-VP200LDHW 7.4.5 How to use with Terminal PAW-VP-RTC5B-ECO PAW-VP-RTC5B-ECO PAW-VP-RTC5B-ECO PAW-VP1000LDHW PAW-VP380L PAW-VP750LDHW PAW-VP•LDHW - Technical Manual – 2019-11...
Connecting the Refrigerant Tubing Connecting the Refrigerant Tubing Use soldering method Many of conventional split system air conditioners employ the flaring method to connect refrig- erant tubes which run between indoor and outdoor units. In this method, the copper tubes are soldering at tank end.
● ECOi setup for 3 ways system ● Expansion valve ECOi setup when cooling and heating demand is needed Choose the right expansion valve for different tank models PAW-VP-VALV-280 PAW-VP-VALV-160 PAW-VP1000LDHW PAW-VP500LDHW PAW-VP750LDHW PAW-VP200LDHW PAW-VP380L PAW-VP•LDHW - Technical Manual – 2019-11...
How to make Settings How to make Settings Detailed settings for indoor unit The settings must be made after switching on the power supply but before regular operation! 9.1.1 Setting procedure for remote controller model CZ-RTC5B 20:30 (THU) ] START CZ-RTC5B Operating procedure 1.
Page 101
How to make Settings 3. Select the “Code no.” by pressing the button. Change the “Code no.” by pressing button (or keeping it pressed). 4. Select the “Set data” by pressing the button. Select one of the “Set data” by pressing button.
How to make Settings 9.1.2 Detailed setting procedure for remote controller model RTC4 This allows the system address, indoor unit address, and other settings to be made for the individual or group-control indoor unit to which the remote controller used for detailed settings is connected.
How to make settings on outdoor unit How to make Settings 9.1.3 Detailed setting procedure for remote controller model RTC2 Proceed as follows: 1. Press and hold the buttons simultaneously for 4 seconds or longer. 2. Press the temperature setting buttons to select the item code to change.
How to make Settings Detailed settings for indoor/outdoor unit RTC5B/RTC2/4 The new value must be set during the commissioning U-100PZH2E5/VP200LDHW Tank controller CZ-RTC5B detailed settings Explanation Check and adjust Parameter Default value New value to set 0031 0031 Water unit 0012 0012 Indoor capacity type 100...
Page 105
Condensing temperature upper limit -002 Condensing temp. offset from -2 k to 0 k Frost adherence temp. change from -2 °C to -4 °C ECOi U-10ME2E8 ECOi U-16MF3E8 / PAW-VP1000LDHW PAW-VP750LDHW Tank controller CZ-RTC5B detailed settings Explanation Check and adjust...
How to make Settings Monitoring operations (Sensor info) 9.3.1 How to open the sensor menu Proceed as follows: Press the button to scroll thrugh see Sensor info. 20:30 (THU) each menu. Unit no. Code no. Data If you wish to see the next screen instantly, press 0026 0028 button.
How to make Settings 9.3.3 Monitoring operations (Sensor info) ECOi Description Remarks Indoor unit intake temp. (TA) °C Indoor unit heat exchanger temp. E1 (E1) °C — Indoor unit heat exchanger temp. E3 °C Indoor unit Discharge air temp. (BL) °C Discharge air temp.
Error Codes PACi & ECOi 10 Error Codes PACi & ECOi Alarm codes for indoor/outdoor units PACi Alarm Code Alarm Meaning Remote controller reception error Remote controller transmission error Error in indoor unit receiving signal from remote controller (central) Error in indoor unit receiving signal from the outdoor unit. No communication from the outdoor unit for 3 minutes Abnormal indoor/outdoor communication error Outdoor unit failed to receive serial communication signals from indoor unit Dublicate indoor unit address settings error...
Page 109
Error Codes PACi & ECOi Alarm codes for indoor/outdoor units ECOi Remote control Alarm contents display Two or more indoor units are set as main, in the group controlled indoor units Fewer indoor units are found in Auto addressing than the setting on outdoor PCB. More indoor units are found in auto addressing than the setting on outdoor PCB No response from sub indoor to the main indoor unit in group control wiring No indoor unit responded in auto addressing...
Page 110
Error Codes PACi & ECOi Remote control Alarm contents display Thermal protector for indoor unit fan motor is activated Compressor discharge temperature is too high High pressure switch is activated AC power supply has abnormal Connection to the panel of indoor unit is not good Float switch of drain pan safety is activated Drain pump failure or locked rotor Indoor unit fan inverter protection control is activated.
Check Before Requiring Services Check Before Requiring Services 11.1 Factory pre-installed Back-up heater Trouble shooting Before you contact your dealer, check following points: Symptom Cause Remedy Press ON/OFF operation button on remote controller again. Power failure or after power failure Ait-to-Water unit does not run at Operation button is turned off.
Check Before Requiring Services 11.2 Electrical connection check points PAW-VP200LDHW, PAW-VP500LDHW 230V Electrical connection single phase 230 V Symbol Description Electric heating element Thermostat safety device Power supply line L1, L2 Electric line connection terminals S1, S2 Thermostat contacts Contact operated Ground ...
Page 113
Check Before Requiring Services PAW-VP750LDHW, PAW-VP1000LDHW 400V Electrical connection three phase 400 V Thermostat Heating element 400V Symbol Description Electric heating element 1, 2, 3, 4, 5, 6 Heating elements contacts 11R, 21S, 31T Thermostat-out contacts Thermostat safety device...
Legionella Protection Control 12 Legionella Protection Control Legionella protection cycle ● At least once a week, the heating element must be activated until the minimum temperature in the tank is reached at 63 degrees. ● Minimum ON time 3 hrs. ●...
Booster Heater for PAW-VP380L 13 Booster Heater for PAW-VP380L Optional part: Installation and Service Manual 13.1 Installation of the heating unit How to mount the heating unit Proceed as follows: 1. Screw the heating unit (1) into the unit seat (ensure the appropriate tightness of the connection) 2.
Booster Heater for PAW-VP380L 13.2 Electrical connection 13.2.1 Connection for 3 phases (Star) 400 V AC power supply Bridge connection Controller connections 400 V AC supply Heater 1 Cable to remove between N-L2 Heater 3 Heater 2 13.2.2 Connection for 3 phases (Triangle) 230 V 3 phase AC power supply Bridge connection Heater 1...
Booster Heater for PAW-VP380L 13.3 Start-up and service 13.3.1 Operation keys and displays The heater and protecting box equipped with the temperature controller is a simple unit serving to control the heating process. The unit controls the heater or set of the electric heaters which are supplied from the power supply 230 V AC (1or 3 phase) or 400 V AC (3 phase).
Page 118
Booster Heater for PAW-VP380L Also, the other information can be seen on the display. All reminders and their description are specified in the following table: Information Acoustic Alarm diode Description displayed alarm Flashing Variable Lack or failure of the sensor. Alarm switches off automatically after repair of the failure.
Booster Heater for PAW-VP380L 13.3.2 Menu diagram The way of moving through the menu is shown in the following diagram. 3 sec 5 sec 3 sec Change of values Range 0–1 3 sec Change Change of values of values Range 15–160 °C Range 1–10 °C Important Return from the setting mode is executed automatically after approximately 5 seconds from the...
Booster Heater for PAW-VP380L 13.3.3 Operational menu The operational menu is available when the controller operates in the switched on mode (ON). One pressing of or push-button during displaying the temperature causes entering the SETTINGS OF TEMPERATURE mode. Keeping the push-button pressed for 3 seconds while the temperature displaying causes entering the SETTINGS OF HYSTERESIS.
Referring to EU Commission Delegated Regulation No. 812/2013 Supplier's name or trademark Polar Energi AS, Norway Supplier's model identifier PAW- VP200LDHW PAW- VP500LDHW PAW- VP750LDHW PAW-VP1000LDHW Declared load profile Water heating energy efficiency class A+++ Water heating energy efficiency 211,0% 180,0%...
Appendix A.5. Information sheet: Heat pump space heaters Referring to EU Commission Delegated Regulation No. 811/2013 Models: PAW-VP380L + U-200PZH2E8 Air-to-water heat pump: Water-to-water heat pump: Brine-to-water heat pump: Low-temperature heat pump: Equipped with a supplementary heater: Heat pump combination heater: Average Climate Conditions: Item Symbol...
Page 130
DECLARATION OF CONFORMITY Manufacturer’s name & address Polar Energi As Postboks 117 9450 Hamnvik, Norway Object of declaration, Polar Energi product name and model: PAW-VP 1000L-DHW • • PAW-VP 750L-DHW PAW-VP 500L-DHW • PAW-VP 200L-DHW • to which this declaration relates is in conformity with following directives and requirements: EC directive on: •...
Page 131
DECLARATION OF CONFORMITY Manufacturer’s name & address Polar Energi As Postboks 117 9450 Hamnvik, Norway Object of declaration, Polar Energi product name and model: • PAW-VP 380L to which this declaration relates is in conformity with following directives and requirements: EC directive on: •...
Page 134
Polar Energi AS Postboks 117 9450 Hamnvik Norway www.polarenergi.com...