Tube Flow Scan
The Tube Flow Scan function allows the user to measure the
air flow rate for a selected set of tubes.
Procedure:
1.
2.
3.
4.

Configuration Options

All of the configuration options described in VEA-040-Axx product guide are available with the following deviations
VESDAnet options are not applicable as VESDAnet is not user accessible for the SLC enabled detectors.
Module options are not applicable to SLC enabled VEA detectors as it doesn't support Expansion StaX and Local Relay StaX.
Flow thresholds (Fault Sensitivity) and Flow Fault delay parameters can only be set by the fire panel. These settings are not available in the
VSC software.
Refer to respective panel guide to set the air flow parameters. The remaining flow parameters defined in VEA-040-Axx product guide can be set
using the VSC software. Follow the VEA-040-Axx product guide for information on setting up the remaining parameters.
GPIs and Relays
General purpose inputs are not available to be configured via VSC.
Relay options are not available to be configured via VSC. The following screen shot shows relay assignments for the SLC instance.
8
– The Flow rate can be viewed in the event log.
Select Tube Flow Scan from the Device Menu.
Select the tubes for which the flow scan is to be
performed.
Select Start. "Testing In Progress" will be displayed. The
detector will move the rotary valve to each tube and
measure the flow rate.
To stop the flow scan select "Stop". The event log will
have an event showing the flow rate for each selected
tube.
VEA Product Guide — P/N LS10215-000NF-E:A 07/24/2018