NCI/Field
FilterFlow
nciFlowSP
StbyMinFlowPos
UnOcMinFlowPos
MinFlowPos
MaxFlowPos
ReheatFlowPos
EmergPress
EmergDePress
EmergPurge
Warmup
NightPurge
WindowOpen
Table 23. Configuration Parameters (Continued)
AP
Net Data
Default
Internal
Type
Val
Units
ubyte
0
SNVT
0
lev_percent
SNVT
0
lev_percent
SNVT
15
lev_percent
SNVT
60
lev_percent
SNVT
20
lev_percent
SNVT
100
lev_percent
SNVT
0
lev_percent
SNVT
50
lev_percent
SNVT
50
lev_percent
SNVT
50
lev_percent
SNVT
0
lev_percent
Airflow low pass (10 sec time constant) filter enable. Warning:
Enable filter only when the pressure pickup is installed in a
turbulent airflow environment with unstable airflow control issues.
0: filter disabled
1: filter enabled
Notes:
Set nciFlowLoop.DeadBand = 30 fpm when filter enabled
%
VAV Box standby mode of operation minimum flow setpoint in
damper position percent. Applies only to pressure dependent
control mode.
0
range
MaxFlowPos
Precision: 1
%
VAV Box unoccupied mode of operation minimum flow setpoint in
damper position percent. Applies only to pressure dependent
control mode.
0
range
MaxFlowPos
Precision: 1
%
Zone terminal minimum cooling flow setpoint during the occupied
mode of operation. Applies only to pressure dependent control
mode or when a pressure independent airflow sensor fails.
0
range
MaxFlowPos
Precision:1
%
VAV Box Maximum Cooling flow value in damper position percent.
Applies only to pressure dependent control mode or when a
pressure independent airflow sensor fails.
0
range
100%
Precision:1
%
VAV Box Reheat cooling air value in damper position percent. The
cooling air damper will be at the ReheatPos at maximum reheat
capacity.
0
range
MaxFlowPos
Precision: 1
%
Emergency pressurization setting as a percent of maximum flow.
0
range
100%
Precision: 1
%
Emergency depressurization setting as a percent of maximum
flow.
0
range
100%
Precision: 1
%
Emergency purge setting as a percent of maximum flow.
0
range
100%
Precision: 1
%
Warmup setting as a percent of maximum flow.
0
range
MaxFlowPos
Precision: 1
%
Night purge setting as a percent of maximum flow.
0
range
MaxFlowPos
Precision: 1
%
Window open damper position. When a window is open, air flow
control is disabled, the flow damper is set to WindowOpenPos until
the space temperature drops below the temperature set point.
0
range
MaxFlowPos
Precision: 1
91
Description
31-00083—02