Honeywell CVL4022ASVAV1 Engineering Manual page 24

Stryker lon vav system
Table of Contents

Advertisement

CONFIGURATION
Option
Damper Control
Fan
Type of Reheat Coil
Type of Peripheral Heat
Window Open Option
Monitor switch Option
Occupancy Sensor Option
Heat/Cool Changeover
Switch Option
Wall Module Option
Air Temperature Sensor
31-00083—02
Table 12. Some important Configuration Options
1. Series 60 floating actuator
2. Pulse width modulating actuator
3. Analog actuator
1. None
2. Parallel Temperature
3. Parallel Flow
4. Parallel Analog
5. Series
1. One stage
2. Two stages
3. Three stages
4. Series 60 Modulating electric valve, or pneumatic via transducer
5. Pulse Width Modulating electric valve, or pneumatic via transducer
6. Analog
1. One stage
2. Series 60 Modulating electric valve
3. Pulse Width Modulating electric valve
4. Analog
1. Network input
2. Local Window Open Digital Input - directly wired to the controller. (Configurable as
normally open / closed.)
1. Network input
2. Local Monitor switch (general purpose) Digital Input - directly wired to the controller.
(Configurable as normally open / closed.)
1. Network input
2. Local Occupancy sensor Digital Input - directly wired to the controller. (Configurable as
normally open / closed.)
1. None
2. Local Heat/Cool change over switch Digital Input directly wired to the controller. (Contacts
closed means select Heat Mode.)
1. Local (direct wired to the box). Both T7770/TR2X models and the Sylk-based Zio (TR71/
T5) models are supported
2. Shared (wired to another box) and shared via Lon network
1. Discharge Air Temperature
2. Supply Air Temperature
3. Outdoor air temperature and humidity
AscLon VAV Possible Configurations