Code Error Causes
44
Use of Timer
Index error
50
Error of external
device is detected
by a user
program during
operation
60
E_STOP function
execution
101
CPU position
error
102
Duplicated CPU
ID error
103
Base abnormal
error
104
System
configuration
error
Measures
Restart mode after the
measure.
Modify the timer index
program, reload, and
start.
Repair a fault device by
referring to error
detection flag of external
device and restart
(according to
parameter).
Eliminate the causes of
error operating E_STOP
function in the program
and turn it on again.
CPU is installed at
wrong position. Position
the CPU correctly.
Set the A/B side
switches of master CPU
and standby CPU
differently.
Configure the expansion
cable as ring topology
and position the
detached base correctly.
For information of
detached base, refer to
the CPU error log.
Check for dual IO link
redundancy
configuration and ring
topology.
Check redundancy
l
drive module station
number.
Check the version of
l
the operating system
of the expansion drive
module and the
expansion manager.
- 59 -
Chapter 4 - Troubleshooting
Operation
LED
Status
Status
STOP
RUN:
(RUN)
OnERR :
On
STOP
ERR : On
(RUN)
(P.S. :
On)
STOP
RUN:
OnERR :
On
STOP
S101
STOP
S102
STOP,
E103
RUN
STOP
E104
Diagnostic
Timing
When scan
ends.
When scan
ends.
When
program is
executed.
Turn it on.
Turn it on.
Execute
program.
When the
scan ends,
turn it on.