Door Alarm; Water Alarm; Smoke Alarm - Huawei Telecom Power TP48120A-HD15A1 User Manual

Hide thumbs Also See for Telecom Power TP48120A-HD15A1:
Table of Contents

Advertisement

TP48120A-HD15A1, TP48120A-HD15A2,
TP48200A-HD15A1, and TP48200A-HD15A2 Telecom
Power
User Manual
Measures
1.
2.
3.

4.2.16 Door Alarm

Possible Causes
Measures
1.
2.

4.2.17 Water Alarm

Possible Causes
Measures
1.
2.

4.2.18 Smoke Alarm

Possible Causes
Issue 03 (2020-01-04)
Check whether the battery undertemperature alarm threshold (-10° C by default) is
properly set. If no, adjust it to a proper value.
Check whether the battery temperature controlling system is faulty. If yes, rectify the
fault. The alarm is cleared when the battery temperature falls within the allowed range.
Check whether the battery temperature sensor is faulty. If yes, replace the temperature
sensor.
This alarm is generated only for the power system that has door status sensor installed.
The cabinet doors are open.
The door status sensor is faulty.
Close cabinet doors.
Check whether the door status sensor is faulty. If yes, replace the door status sensor.
This alarm is generated only for the power system that has water sensors installed.
Water intrudes into the cabinet.
The water sensor is faulty.
Check whether water intrudes into the cabinet. If yes, wipe the water with dry cotton or
other tools and rectify the fault.
Check whether the water sensor is faulty. If yes, replace the water sensor.
This alarm is generated only for the power system that has smoke sensors installed.
There is smoke inside the cabinet.
The smoke sensor is faulty.
Copyright © Huawei Technologies Co., Ltd.
4 Maintenance
46

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents