Indicator
Color
Alarm indicator
Yellow
Fault indicator
Red

3.4 SMU06C

Figure 3-7 SMU06C panel
(1) Alarm indicator
Issue 03 (2020-01-04)
Status
Off
Blinking at 0.5 Hz
Blinking at 4 Hz
Off
Steady on
Blinking at 0.5 Hz
Off
Steady on
(2) Run indicator
Copyright © Huawei Technologies Co., Ltd.
Description
The rectifier has no AC power input.
The rectifier is faulty.
The rectifier is being queried.
The rectifier is loading an application program.
No alarm is generated.
The rectifier generates an alarm for power
limiting due to ambient overtemperature.
The rectifier generates an alarm for shutdown
due to ambient overtemperature or
undertemperature.
The rectifier protects against AC input overvoltage
or undervoltage.
The rectifier is hibernating.
The communication between the rectifier and the
SMU is interrupted.
The rectifier is running properly.
The rectifier locks out due to output overvoltage.
The rectifier has no output due to an internal fault.
3 Components
(3) LCD
29