APPLICATION
The T810D and TS810B are low voltage, spst controls
for heating systems.
The T810D is for 24 Vac control of heating-only systems.
The TS810B can control 750mV circuits.
A positive Off feature is available on the TS810B and
select T810D models.
Heat anticipation is fixed in most models. The current
rating is stamped on the thermostat. TheT810D has an
adjustable heat anticipator rating of 0.18A to 0.8A at
30 Vac. See Fig. 1.
MERCURY NOTICE
If this control is replacing a control that contains
mercury in a sealed tube, do not place your old
control in the trash.
Contact your local waste management authority
for instructions regarding recycling and the
proper disposal of the old thermostat.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the Instructions and on
the product to make sure the product is suitable for
your application.
® U.S. Registered Trademark
© 2003 Honeywell International Inc. •
T810D; TS810B Heating
3. Installer must be a trained, experienced service
4. After installation is complete, check out product
Location
Locate the thermostat about 5 ft (1.5m) above the floor in
an area with good air circulation at average temperature.
Do not mount the thermostat where it can be affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat
IMPORTANT
The wiring run for TS810B millivolt systems should be
kept as short as possible.
• All Rights Reserved
Thermostats
INSTALLATION INSTRUCTIONS
technician.
operation as provided in these instructions.
CAUTION
Electrical Hazard.
Can cause personal shock or equipment
damage.
Disconnect power supply before beginning
installation.
This is a precision instrument. Rough handling
can decrease its accuracy. Handle it carefully.
69-1160B-1

Advertisement

loading

Summary of Contents for Honeywell T810D

  • Page 1 The T810D and TS810B are low voltage, spst controls operation as provided in these instructions. for heating systems. CAUTION The T810D is for 24 Vac control of heating-only systems. The TS810B can control 750mV circuits. Electrical Hazard. Can cause personal shock or equipment A positive Off feature is available on the TS810B and damage.
  • Page 2: Wiring And Mounting

    ADJUSTABLE HEAT 4. Adjust the heat anticipator (T810D models only) to ANTICIPATOR SCALE match the current draw of the primary control in the system. See Heat Anticipator Setting (T810D) sec- BIMETAL ELEMENT BEHIND tion.
  • Page 3: Settings And Checkout

    (or within) the rating of Equipment Damage Hazard. the heat anticipator. Shorting across system controls can damage 2. The T810D Thermostat is equipped with an heat anticipator. adjustable heat anticipator and operates cor- Do not short across system control terminals to rectly only if this heater is adjusted to match the check system operation.
  • Page 4 T810D; TS810B HEATING THERMOSTATS Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 69-1160B-1 G.H. Rev. 1-03 www.honeywell.com/yourhome...
  • Page 5: Notice D'installation

    Couper l'alimentation avant d'effectuer systèmes de chauffage. l'installation. Le T810D est un thermostat pour les systèmes de chauffage seulement de 24 V c.a. Le TS810B peut Emplacement commander les circuits de 750 mV. Installer le thermostat à environ 1,5 m (5 pi) du plancher dans un endroit bien aéré...
  • Page 6 MF11700 MUR OU SUR UNE BOþTE DE JONCTION) COUPURE ET UNE PROTECTION CONTRE LES SURCHARGES. MF3607 Fig. 1. Schéma interne du T810D avec anticipateur de Fig. 2. Le T810D dans un système type chaleur réglable. de chauffage au gaz. Câblage et montage Tout le câblage doit être conforme aux codes et aux...
  • Page 7 Étalonnage Ce thermostat a été étalonné avec soin à l'usine; Le T810D est muni d'un anticipateur de chaleur pouvant normalement, il n'y a pas lieu de l'étalonner sur place. être réglé de 0,18 A à 0,8 A sous 30 V c.a. L'anticipateur S'il semble déréglé, suivre les instructions suivantes :...
  • Page 8 THERMOSTATS DE CHAUFFAGE T810D ET TS810B Solutions de régulation et d'automatisation Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35, Dynamic Drive Golden Valley, MN 55422 Scarborough (Ontario) M1V 4Z9 69-1160B-1 G.H. Rév. 01-03 www.honeywell.com/yourhome...

This manual is also suitable for:

Ts810b