Six relay control module

Advertisement

2
1
Figure 4b: Installation of IDP-Relay-6 module in
front chassis position
Step 1: Insert the bottom edge of the IDP-Relay-6
module down into a front slot of the chassis.
Step 2: Carefully swing the upper edge of the board
towards the back of the chassis until it touches
the 1
1
/
˝ (31.75mm) standoffs installed on the
4
rear module.
Step 3: Align two 4-40 screws with the two standoffs and tighten.
Step 4: Address and wire the modules according to
the instructions in this manual.
WIRING
NOTE: All wiring must conform to applicable local
codes, ordinances, and regulations.
1. Install module wiring in accordance with the job draw-
ings and appropriate wiring diagrams.
2. Make electrical connections by stripping approxi-
mately
1
/
˝ (6.35mm) of insulation from the end of the
4
wire sliding the bare end of the wire under the clamp-
ing plate, and tightening the clamping plate screw.
3. Set the address on the modules per the job drawing.
Use the rotary code switches to set the address of the
first module (between 01 and 94). The remaining mod-
ules are automatically assigned to the next five higher
addresses. For example, if the base address switch is
set to 28, the next five modules will be addressed to
29, 30, 31, 32, and 33. DO NOT set the lowest address
above 94, as the other modules will be assigned to
nonexistent addresses.
4. A shunt is provided to disable a maximum of three
unused modules. Modules are disabled from the high-
est address and work downward. If two modules are
disabled, the lowest four addresses will be functional,
while the highest two will be disabled. For example, if
the shunt for Address Disable is placed on "two" and
the base address switch is set to 28, the modules will
be assigned to 28, 29, 30 and 31.
NOTE: The IDP-Relay-6 must have power cycled for
shunt changes to take effect.
K200-15-00
NOTES:
• The relay contacts on the IDP-Relay-6 may be
connected to either a power-limited or non power-
3
limited source, this wiring must remain separated by at
1
least
/
˝ (6.35 mm) from all power-limited wiring.
4
• Power-limited circuits must employ type FPL, FPLR, or
FPLP cable as required by Article 760 of the NEC.
• For easier wiring, assign all power-limited wiring to one
side rather than alternating with non power-limited.
C0245-00
PROGRAMMING
The modules are programmed as modules in each system
according to the programming instructions in the appro-
priate FACP manual.
3
I56-2732-003