Section 4
Protection functions
Table 350:
PHLPTOC Group settings (Advanced)
Parameter
Type of reset curve
Table 351:
PHLPTOC Non group settings (Basic)
Parameter
Operation
Num of start phases
Curve parameter A
Curve parameter B
Curve parameter C
Curve parameter D
Curve parameter E
Table 352:
PHLPTOC Non group settings (Advanced)
Parameter
Minimum operate time
Reset delay time
Measurement mode
Table 353:
PHHPTOC Group settings (Basic)
Parameter
Start value
Start value Mult
Time multiplier
Operate delay time
Operating curve type
322
Values (Range)
Unit
1=Immediate
2=Def time reset
3=Inverse reset
Values (Range)
Unit
1=on
5=off
1=1 out of 3
2=2 out of 3
3=3 out of 3
0.0086...50000.000
0
0.0000...0.7120
0.02...6.00
0.46...30.00
0.0...1.0
Values (Range)
Unit
20...60000
ms
0...60000
ms
1=RMS
2=DFT
3=Peak-to-Peak
5=Wide P-to-P
Values (Range)
Unit
0.10...40.00
xIn
0.8...10.0
0.025...15.000
40...300000
ms
1=ANSI Ext. inv.
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
Step
Default
1=Immediate
Step
Default
1=on
1=1 out of 3
1
28.2000
1
0.1217
1
2.00
1
29.10
1
1.0
Step
Default
1
20
1
20
2=DFT
Step
Default
0.01
0.10
0.1
1.0
0.005
1.000
10
40
15=IEC Def. Time
1MRS759142 C
Description
Selection of reset curve type
Description
Operation Off / On
Number of phases required for operate
activation
Parameter A for customer programmable
curve
Parameter B for customer programmable
curve
Parameter C for customer programmable
curve
Parameter D for customer programmable
curve
Parameter E for customer programmable
curve
Description
Minimum operate time for IDMT curves
Reset delay time
Selects used measurement mode
Description
Start value
Multiplier for scaling the start value
Time multiplier in IEC/ANSI IDMT curves
Operate delay time
Selection of time delay curve type
Technical Manual
REX640