8.3 MODBUS MEMORY MAP
Table 8–6: 745 MEMORY MAP (Sheet 20 of 57)
GROUP
ADDR
(HEX)
DEFAULT
1043
MESSAGES
1045
continued
1047
1049
104B
104D
104F
1051
1053
1055
1057
1059
105B
105D
105F
SCRATCHPAD
1060
1074
1088
109C
10B0
10C4
10CF
DNP
10D0
10D1
10D2
10D3
8
10D4
10D5
10D6
10D7
10D8
10D9
10FF
TRANSFORMER
1100
1101
8-36
DESCRIPTION
Default Message #18 (2 registers)
Default Message #19 (2 registers)
Default Message #20 (2 registers)
Default Message #21 (2 registers)
Default Message #22 (2 registers)
Default Message #23 (2 registers)
Default Message #24 (2 registers)
Default Message #25 (2 registers)
Default Message #26 (2 registers)
Default Message #27 (2 registers)
Default Message #28 (2 registers)
Default Message #29 (2 registers)
Default Message #30 (2 registers)
Reserved
Reserved
Scratchpad Message 1 (20 registers)
Scratchpad Message 2 (20 registers)
Scratchpad Message 3 (20 registers)
Scratchpad Message 4 (20 registers)
Scratchpad Message 5 (20 registers)
Reserved
Reserved
Port Used For DNP
Include User Map Points (Point Mapping)
Transmission Delay
Data Link Confirmation Mode
Data Link Confirmation Timeout
Data Link Confirmation Retries
Select/Operate Arm Timer Duration
Write Time Interval
Inhibit Cold Restart
Reserved
Reserved
Nominal Frequency
Phase Sequence
745 Transformer Management Relay
8 COMMUNICATIONS
RANGE
STEP
UNITS
VALUE
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
0 to 65000
1
ms
---
---
---
1 to 65000
1
ms
0 to 100
1
---
1 to 65000
1
ms
0 to 65000
1
ms
---
---
---
50 to 60
10
Hz
---
---
---
FORMAT
FACTORY
CODE
DEFAULT
F32
---
F32
---
F32
---
F32
---
F32
---
F32
---
F32
---
F32
---
F32
---
F32
---
F32
---
F32
---
F32
---
F33
"Text 1"
F33
"Text 2"
F33
"Text 3"
F33
"Text 4"
F33
"Text 5"
F99
0 = None
F30
1 = Enabled
F1
0 ms
F102
0 = Never
F1
1000 ms
F1
3
F1
10000 ms
F1
0 ms
F30
0 = Disabled
F1
60 Hz
F27
0 = ABC