Samsung AM JXVHGH Series Installation Manual page 43

Table of Contents

Advertisement

Size of the pipe between branch joints (B)
Select the pipe size according to the sum of indoor unit capacity which will be connected after the branch .
❇ However, if the size of the pipe between branch joints (B) is bigger than the size of the pipe connected to the
outdoor unit (A), apply the pipe size (A) .
Indoor unit capacity (kW)
15 .0 kW and below
Over 15 .0 kW ~ 22 .4 kW and below
Over 22 .4 kW ~ 28 .1 kW and below
Over 28 .1 kW ~ 33 .6 kW and below
Over 33 .6 kW ~ 45 .0 kW and below
Over 45 .0 kW ~ 50 .4 kW and below
Over 50 .4 kW ~ 63 .3 kW and below
Over 63 .3 kW ~ 70 .3 kW and below
Over 70 .3 kW ~ 98 .4 kW and below
Over 98 .4 kW ~ 105 .5 kW and below
Over 105 .5 kW ~ 135 .2 kW and below
Over 135 .2 kW ~ 169 .0 kW and below
Over 169 .0 kW
Size of the pipe between the branch joint and the indoor unit
Make a selection according to outdoor unit capacity .
Indoor unit capacity (kW)
6 .0 kW and below
7 .2 kW ~ 16 .0 kW and below
20kW ~ 23 .0 kW and below
Over 23 .0 kW
DVM S HE_IM_DB68-05461A-08_EN.indd 43
Pipe size (mm)
Liquid pipe
Low pressure gas pipe
Ø 15 .88
Ø 9 .52
Ø 19 .05
Ø 22 .22
Ø 12 .70
Ø 28 .58
Ø 15 .88
Ø 34 .92
Ø 19 .05
Ø 41 .28
Ø 22 .22
Ø 53 .98
Pipe size (O.D. mm)
Liquid pipe
Ø 6 .35
Ø 9 .52
Ø 9 .52
Ø 9 .52
High pressure gas pipe
Ø 15 .88
Ø 19 .05
Ø 22 .22
Ø 28 .58
Ø 34 .92
Ø 41 .28
Gas pipe
Ø 12 .70
Ø 15 .88
Ø 19 .05
Ø 22 .22
43
2017-03-24 오후 1:38:20

Advertisement

Table of Contents
loading

This manual is also suitable for:

Am jxvhgr seriesAm hxvagh seriesAm100jxvagh/euAm120jxvagh/euAm140jxvagh/euAm160jxvagh/eu ... Show all