Honeywell SLATE Series Installation Instructions Manual

Honeywell SLATE Series Installation Instructions Manual

Low torque actuator

Advertisement

SLATE™ Low Torque Actuator
Series
FOR COMMERCIAL AND INDUSTRIAL MODELS
R8001M1050, R8001M1150, R8001M4050, R8001M4150
SLATE Commercial Model
APPLICATION
SLATE brings configurable safety and programmable
logic together into one single platform. The SLATE
program can easily be customized for almost any
application—offering virtually limitless development
opportunities with far less complexity.
The SLATE Low Torque Actuator series includes
commercial- and industrial-grade 1/4-turn actuators
available in 50 and 150 in/lb models with highly
repeatable position accuracy designed specifically to
integrate with the SLATE system. This series is well
suited for the precise control of air and gas flow and
can operate in a wide range of temperatures and
environmental conditions.
SLATE™ Low Torque Actuator can be easily mounted
to the following valves using the mounting kits noted
below. These kits can be ordered via
www.customer.honeywell.com.
• Maxon CV Valve Series (1/2"–2")
mounting kit #50123928-001
• Honeywell V51E Valve Series (1-1/2"–2")
mounting kit #50124386-001 and mounting kit
#32003396-001
• Honeywell V51E Valve Series (2-1/2"–4")
mounting kit #50124386-001 and mounting kit
#32003396-002
• Honeywell V5197A Valve Series (3/4"–3")
mounting kit #50124386-001
INSTALLATION INSTRUCTIONS
FEATURES AND BENEFITS
• Offered in two different configuration options:
NEMA 1 rated, operating in a temperature
range of -18 to 158 °F (-28 to 70 °C) with
450 positions over a 90° span
NEMA 4 rated, operating in a temperature
range of -40 to 158 °F (-40 to 70 °C) with
900 positions over a 90° span
• Field-reversible clockwise and counterclockwise
rotation operation.
• Internal temperature, valve status, health
diagnostics, and error codes reporting.
• Robust, heavy-duty construction, continuous
duty cycle-rated.
• Closed loop position control via Modbus RS-485
communications as an input to the SLATE Fuel
Air Ratio Module, part R8001C6001.
• Dual 1/2-in knockout conduit connections.
• 1/2-in keyed output shaft with a 1/8-in square
key.
• Die-cast aluminum base with high-impact
resistant, reinforced plastic cover.
• Meets UL353 Safety for Limit Controls.
• Meets UL1998 when used with R8001C6001
SLATE Fuel Air Ratio Module.
APPROVALS
Underwriters
Meets UL353 Safety for Limit
Laboratories
Controls.
Meets UL1998 when used with
R8001C6001 SLATE Fuel Air Ratio
Module.
CE
2009/142/EC: Gas Appliance
Directive
(EN 12067-2:2004, EN298-2012)
32M-06009-06

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell SLATE Series

  • Page 1 These kits can be ordered via (EN 12067-2:2004, EN298-2012) www.customer.honeywell.com. • Maxon CV Valve Series (1/2"–2") mounting kit #50123928-001 • Honeywell V51E Valve Series (1-1/2"–2") mounting kit #50124386-001 and mounting kit #32003396-001 • Honeywell V51E Valve Series (2-1/2"–4") mounting kit #50124386-001 and mounting kit #32003396-002 •...
  • Page 2: Specifications

    SLATE™ LOW TORQUE ACTUATOR SERIES SPECIFICATIONS Vibration: Honeywell V2 test specification; 3 axes tested as follows: 2-Hour Performance/Resonant Detection Sweep: Supply Voltage (Peak Current): Vibration sinusoidal: 5 Hz - 30 Hz; DC model: 24VDC +10/-20% Amplitude: 0.012mil pk/pk75 mm Vibration sinusoidal: 30 Hz – 300 Hz at 0.6G Power: Endurance: 1.1G for 2 hours at resonant frequen-...
  • Page 3: Installation Instructions

    The SLATE Actuator must be set up and maintained in the field by qualified NOTICE personnel. If the equipment is used in a Language translations for this document are available manner not specified, the protection provided at www.customer.honeywell.com. by the equipment may be impaired. 32M-06009—06...
  • Page 4: Electrical Installation

    SLATE™ LOW TORQUE ACTUATOR SERIES Mounting See Fig. 2 for the locations of the mounting holes. The mounting holes are threaded for M6 x 1 x 1/2-in The actuator assembly may be installed in any (12mm) fasteners. orientation. 1-1/8 O 1/4 (6) X 17/64 (7) (28) 2X 3-1/2 (89) WARNING...
  • Page 5: Input Power

    SLATE™ LOW TORQUE ACTUATOR SERIES 4. In addition to a grounded conduit, the use of shielded, twisted-pair cable is strongly recom- mended for DC power and signal wires. The shield drain wires should be landed to chas- sis/earth on both ends of the cable, but ONLY if a conduit is also grounded on both ends.
  • Page 6 SLATE™ LOW TORQUE ACTUATOR SERIES Table 2. Wiring Terminal Identification. Type Terminal Description Wiring PE (Protective Earth) Chassis Chassis connection for mains Follow local codes for safety earth ground screw power and shield/drain wires installation. See Electrical installation section for shield drain installation instructions.
  • Page 7: Troubleshooting

    SLATE™ LOW TORQUE ACTUATOR SERIES OPERATING INSTRUCTIONS TROUBLESHOOTING The SLATE Actuator is designed specifically for the If the two shafts are not perfectly and concentrically SLATE Fuel Air Ratio Module. For actuator operation aligned, additional binding and torque will be and programming information, see the SLATE Fuel Air introduced into the assembly causing error codes to Ratio Module document 32-00006 and other SLATE...
  • Page 8 All other components, not listed in the table, do not contain restricted substances above the threshold level For More Information The Honeywell Thermal Solutions family of products includes Honeywell Combustion Safety, Eclipse, Exothermics, Hauck, Kromschröder and Maxon. To learn more about our products, visit ThermalSolutions.honeywell.com or contact your...

This manual is also suitable for:

Slate r8001m1050Slate r8001m4050Slate r8001m1150Slate r8001m4150

Table of Contents