Auxiliary Switches; Auxiliary Potentiometers - Honeywell ML6161 Series Product Data

Non-spring return direct coupled actuators
Table of Contents

Advertisement

1
L1
(HOT)
L2
4-20 mA CONTROLLER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
Fig. 13. ML7161 or ML7174 used with 2-10 Vdc control.
1
L1
(HOT)
L2
2-10 Vdc CONTROLLER
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
Fig. 14. ML7161 or ML7174 used with 4-20 mA control.

Auxiliary Switches

The 201052A or B Auxiliary Switch is used in conjunction with
the actuator. It allows for control of equipment external to the
actuator (for example, electric reheat coils and fan) at an
adjustable point in the stroke (0° to 90°) of the actuator.
The 201052A and B Auxiliary Switches are field-addable. For
mounting instructions, see form 63-2218, provided with the
device.
IMPORTANT
When operating an ML6161 or ML6174 from a two-
position controller, a 201052B Auxiliary Switch is
required for proper operation. See Fig. 12.

Auxiliary Potentiometers

The 200976A,C Auxiliary Potentiometers mount on the face of
the ML6161A,C or ML6174A,C (as shown in Fig. 15). The
potentiometer shaft has a slipping collar. If one of the two
limits of the potentiometer is exceeded, the collar continues to
rotate, causing no damage to the potentiometer itself. To
mount the potentiometer on the actuator:
1. Turn the potentiometer to align the shaft key with the
slot in the potentiometer drive.
2. Tilt the potentiometer slightly so the key faces down
toward the slot.
3. Insert the potentiometer into the slot, and push down so
the potentiometer is flush with the actuator body and the
bracket is aligned over the screw hole.
4. Insert the screw provided into the hole and fasten
securely.
35 AND 70 LB-IN. NON-SPRING RETURN DIRECT COUPLED ACTUATORS
ML7161, ML7174
T1
T2
+
+ mA
+ V
M18071
ML7161, ML7174
T1
T2
+
+ mA
+ V
M18072
IMPORTANT
Failure to follow the calibration procedures can result
in improper resistance values at desired stroke.
MOTOR
POSITION
FULLY CW
24V (COM-CW)
FULLY CCW
24V (COM-CCW)
MOTOR
ROTATION
CCW
CW
FIELD-ADDABLE AUXILIARY POTENTIOMETER
Fig. 15. ML6161A,C, ML6174A,C with
field-addable potentiometer.
To Calibrate the 200976A,C:
IMPORTANT
Remove the range stop pins and minimum position
setscrews prior to calibration.
1. Drive the actuator fully closed (0°) to fully open (90°)
and back again to the fully closed position. This must be
done to receive the correct resistance readings at the
appropriate degree of stroke.
2. Check the resistance values of the potentiometer with
an ohmmeter at intervals in the stroke while referring to
the table in Fig. 15 and resistance information provided
in the Specifications section.
3. Replace the range stop pins and/or the minimum
position setscrews using the appropriate procedures.
9
AUXILIARY POTENTIOMETER
RW
RB
RESISTANCE
RESISTANCE
500 OR
0 OHMS
2000 OHMS
500 OR
0 OHMS
2000 OHMS
AUXILIARY POTENTIOMETER LEADS
RW OHMS
RB OHMS
INCREASE
DECREASE
DECREASE
INCREASE
C W
C O M
R
C C W
B
W
M10251B
63-2209—8