Correction Procedures; Factory Settings Restoration; Changing And Setting The Password; Identifying Ied Application Problems - ABB RELION 630 Series Comissioning Manual

Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS756801 E
5.3
5.3.1
5.3.2
5.3.3
630 series
Commissioning Manual
The messages are listed in the LHMI menu under the event list. The signal status data
is found under the IED status and in the internal event list.
Table 7:
Additional indications
Warning indication
Time Synch Error
BATTERY1 Error
Settings Changed
Setting Groups Changed

Correction procedures

Factory settings restoration

In case of configuration data loss or error that prevents the IED from working
properly, the configuration can be restored to the original factory state. All default
settings and configuration files stored in the factory are restored.
For further information on restoring factory settings, contact customer support.

Changing and setting the password

The password can only be set with PCM600.
For more information, see the PCM600 documentation.

Identifying IED application problems

Navigate to the appropriate menu in the LHMI to identify possible problems.
Check that the function is on.
Check that the correct setting group (1 to 4) is activated.
Check the blocking.
Check the mode.
Check the measurement value.
Check the connection to trip and disturbance recorder functions.
Check the channel settings.
Troubleshooting
Additional information
Source of the time synchronization is lost or time
system has made a time reset.
Auxiliary power is disconnected.
Settings have been changed.
Setting group has been changed.
Section 5
33