Setting Up Communication Between Pcm600 And The Ied - ABB RELION 630 Series Comissioning Manual

Hide thumbs Also See for RELION 630 Series:
Table of Contents

Advertisement

1MRS756801 E
2.5
630 series
Commissioning Manual
If the green Ready LED continues to flash after the startup, the IED has detected an
internal error. Navigate via Main menu/Monitoring/IED status to investigate the
error description.
Setting up communication between PCM600 and the
IED
The communication between the IED and PCM600 is independent of the used
communication protocol within the substation or to the NCC.
The communication media is always Ethernet and the used protocol is TCP/IP.
Each IED has an Ethernet interface connector on the front and on the rear side. Both
Ethernet connectors can be used for communication with PCM600.
When an Ethernet-based station protocol is used, PCM600 communication can use
the same Ethernet port and IP address.
For the connection of PCM600 to the IED, two basic variants have to be considered.
Direct point-to-point link between PCM600 and the IED front port.
Indirect link via a station LAN or from remote via a network.
The physical connection and the IP address must be configured in both cases to enable
communication.
The communication procedures are the same in both cases.
1.
If needed, set the IP address for the IEDs.
2.
Set up the PC or workstation for a direct link (point-to-point), or
3.
Connect the PC or workstation to the LAN/WAN network.
4.
Configure the IED IP addresses in the PCM600 project for each IED to match the
IP addresses of the physical IEDs.
Setting up IP addresses
The IP address and the corresponding mask can be set via the LHMI for each available
Ethernet interface in the IED. Each Ethernet interface has a default factory IP address
when the complete IED is delivered.
The default IP address for the IED front port is 192.168.0.254 and the
corresponding subnetwork mask is 255.255.255.0, which can be set via the local
HMI path Main menu/Configuration/Communication/TCP-IP
configuration/Front port.
The default IP address for the IED rear port is 192.168.2.10 and the corresponding
subnetwork mask is 255.255.255.0, which can be set via the local HMI path Main
menu/Configuration/Communication/TCP-IP configuration/LAN1.
Section 2
Starting up
13