Description; Features; Specification; Type Overview - Honeywell LKS 310 Instruction Handbook Manual

Actuator for air dampers on multi-stage and modulating burners
Table of Contents

Advertisement

LKS 310 Actuator for air dampers on multi-stage and modulating burners

DESCRIPTION

A synchronous motor powers an output shaft and a backlashfree
cam shaft via a gear reducer.
The cam shaft operates limit and auxiliary switches. The position
at which one of the limit or auxiliary switches operates can be ad-
justed steplessly within the operating range using the associated
cam disc. Manually adjustable lever-operated cams or spindle-
driven cams, which can be adjusted with a screwdriver, are avail-
able.

SPECIFICATION

Type overview

1)
Clockwise rotation
2)
3)
Diagram
Shaft
Drive
time
Nr.
Nr.
S1
5D
30
S12
5D
30
S7
5B
30
S7
5B
10
S7
5B
15
S12
5D
S7
5C
30
Counter-clockwise rotation
2)
3)
Diagram
Shaft
Drive
time
Nr.
Nr.
S8
5A
3,5
S7
5C
3,5
S7
5B
15
S7
5B
10
Legende
1) when viewing from direction A (see dimensional drawing)
2) see "Circuit diagrams"
3) see "Shaft versions"
4) at 50 Hz for 90°
at 60 Hz, Drive times are about 20 % shorter
5) under nominal conditions
under extreme conditions (e.g. +60 °C, 230V -15%) the torques will be 25% lower
6) +10% -15%; 50...60Hz
at -15%; torque reduced by approx. 20% at undervoltage
7) Standard: Lever-operated cam
2
www.honeywell.com
Load
Holding
4)
5)
torque
torque
s
Nm
Nm
15
10
15
10
15
10
10
10
15
10
7
7
7
15
10
1)
Load
Holding
4)
5)
torque
torque
s
Nm
Nm
3,5
3,5
3,5
3,5
15
10
10
10
honeyvell.energy

FEATURES

Electric actuator up to 15 Nm
• Drive times: 3.5 ... 30 sec.
• Gearing can be decoupled
• Position indicator
• Easily adjustable limit and auxiliary switches
• Synchronous motor
• Particulary stable design in aluminium housing
Variants:
• clockwise or counter clockwise rotation
• with integrated electronic circuitry
• different shaft versions
6)
Voltage
Type
V
230
LKS 310-15 (A-5D-30 S1)
230
LKS 310-21 (A-5D-30 S12)
230
LKS 310-22 (A-5B-30 S7)
230
LKS 310-24 (A-5B-10 S7.1)
230
LKS 310-25 (A-5B-15 S7.1)
110
LKS 310-34 (A-5D-7 S12.1)
230
LKS 310-35 (A-5C-30 S7) IP54
6)
Voltage
Type
V
230
LKS 310-10 (B-5A-3.5 S8)
230
LKS 310-17 (B-5C-3.5 S7.1)
230
LKS 310-31 (B-5B-15 S7.1)
230
LKS 310-32 (B-5B-10 S7.1)
7)
Remarks
Spindle-driven cam
Spindle-driven cam
Spindle-driven cam
7)
Remarks

Advertisement

Table of Contents
loading

Table of Contents