Using The Web Hmi - ABB Relion 630 Series Operation Manual

Power management, compact load-shedding solution
Hide thumbs Also See for Relion 630 Series:
Table of Contents

Advertisement

1MRS757183 F
4.2
PML630/Compact Load-Shedding Solution
Operation Manual
GUID-587B9E5D-17AD-43F5-AE23-5FC09F0D5DAA V2 EN
Figure 49:
Manual load shed confirmation
Table 21:
Manual load shed commands
Command
Manual Shed Subnetwork 1
Manual Shed Subnetwork 2
Manual Shed Subnetwork 3
Manual Shed Subnetwork 4
Selection of priority or power for manual load-shedding action of each
subnetworks is based on the parameter setting in the IED or
communicated input data (from COM600). See the application
engineering guide for more details.

Using the Web HMI

WHMI is disabled by default.
1.
To enable the WHMI, select Main menu/Configuration/HMI/Web HMI/
Operation via the LHMI.
2.
To enable writing through the WHMI, select Main menu/
Configuration/HMI/Web HMI/Write mode via the LHMI.
3.
To open the WHMI, write the IED IP address to the address bar of the
browser.
Description
Manual load shed command for subnetwork 1
Manual load shed command for subnetwork 2
Manual load shed command for subnetwork 3
Manual load shed command for subnetwork 4
Section 4
Using the HMI
61