2.
Power-Reversal Relay Delay
This function sets the delay time before a power
reversal trip occurs. The range of delays is 1 to 1 5
seconds, i n steps o f 1 second. Choosing
power-reversal protection . The Trip Unit display is
shown in Figure 38.
' "
I.LI
Pi
Figure
38.
Trip Unit display for power-reversal relay delay.
Rating Plug Current Setting
The Trip Unit display for rating plug setting is shown
in Figure 39. Enter the current setting of the rating
plug by scrolling through the list with
pressing
when the correct value is reached.
E N T E R
Table 1 6 lists the available rating plugs for the vari
ous Trip Units.
Incorrect storage of this set point will
CAUI'ION:
result in incorrect metering values.
AIT ENTION:
Si une valeur incorrecte est enregistree
pour ce reglage, les mesures seront fausses.
Figure
39.
Trip Unit display for rating plug current set point.
Breaker
disables
O F F
SETUP
s
DElAY
Potential Transformer Primary Voltage
Enter the primary voltage rating of the potential
transformer, as illustrated in Figure 40. The range of
values is 1 20 to 600 volts, with an increment of 1 volt.
and
VALUE
CAUI'ION:
result in incorrect metering values. Even
ting is entered remotely, it must be entered again
locally.
AIT ENTION:
pour ce reglage, les mesures seront fausses. Cette
valeur doit etre enregistree locallement meme dans
le cas d'une utilisation
SETUP
xln
Potential Transformer Connection
Note that this step applies only to MicroVersaTrip
PM Trip Units.
Select the appropriate potential transformer connec
tion, either line-to-line
( Ph -N) , as illustrated in Figure 41 .
22
Frame
Size
Rating Plug Options , Amps
60, 80, 1 00, 1 25, 1 50, 200, 225, 250, 300,
800-
400, 450, 500, 600, 630, 700, 750, 800,
2000 A
900, 1 000, 1 100, 1 200, 1 250, 1 500, 1 600,
2000
2500-
1 200, 1500, 1 600, 2000, 2400, 2500,
3200 A
3000, 3200
1 600, 2000, 2400, 2500, 3000, 3200,
4000 A
3600, 4000
5000 A
3200, 4000, 5000
Table
16.
Trip Unit rating plug options.
Incorrect storage of this set point will
Si une valeur incorrecte est enregistree
a
distance avec commnet.
nvoLTS
' -. L.l
Figure
Trip Unit display for potential transformer primary
40.
voltage set point.
if
this set
SETUP
( Ph - P h )
or line-to-neutral