These 2-position (open/close) control actuators are used with VCZ
1000, 1100, 6000 and 6100 series hydronic valves in a normal
indoor environment to provide quick opening/closing to control the
flow of hot and/or chilled water or glycol solution to 60% concentra
tion. They are designed for on-off "zone" control of heating/cooling
systems, or to control individual fan coil, baseboard radiator or
convector applications.
Depending on the model selected, the actuator can be controlled
by a low or line voltage SPST or SPDT controller, such as a room
thermostat, aquastat or flow switch.
VC80 series valve actuators are designed to be used with hard
wired electronic thermostats with series anticipator or power
stealing thermostats. Recommended control thermostats include
T8601D, T8401C, T8380 and T8360 families.
VC actuators use cam-operated cartridge travel to resist water
hammer. Internal limit switches prevent motor overrun. Some of
these actuators have conformally coated printed circuit boards for
humidity resistance.
2003.02.24
© Honeywell Limited.
On-Off Actuator for VC Series Balanced Hydronic Valves
VC2, VC4, VC60, VC8
The specifications following are nominal and conform to generally
accepted industry standards. Honeywell is not responsible for damages
resulting from misapplication or misuse of its products.
Voltage:
24V 50Hz ; 24V 60Hz Models
100-130 V 50-60 Hz Model
200-240 V 50-60 Hz Model
Power consumption:
6 Watts Max. at nominal Voltage (during valve position change).
Use 24 V Class 2 transformer.
Provide 6 VA per valve for transformer and connection wire sizing.
Maximum Duty Cycle: 15%
Nominal timing: Valve opens in 6 seconds @ 60 Hz (20% longer @
50 Hz)
Electrical termination: Available in 3 versions:
(1) Molex™ (header # 39-30-1060). Requires mating
connector (receptacle/housing # 39-01-2060). OR
(2) integral 1 meter [nominal 39"] leadwire cable.
(3) 5 feet [1.5 meter] plenum-rated cable per UL94-5V.
Includes plastic adapter for use with 3/8" flexible conduit.
End switch rating :
2.2 A inductive from 5 to 110 Vac,
1.0 A inductive above 110 to 277 Vac.
Min. DC switching capability: 5 mA @ 24 Vdc
Operating ambient temperature:
0 to 65°C [32 to 150°F]
Humidity Rating: 5-95% RH (non-condensing)
Fluid temperatures: 34 to 203°F [1 to 95°C]
Shipping & storage temperature: -40 to +65°C [-40 to +150°F]
Atmosphere: non-corrosive, non-explosive
Nominal Dimensions (Actuator only):
3-23/32" width x 2-11/16" depth x 2-3/4" height
94 mm width x 68 mm depth x 70 mm height
272866B Valve Flushing Cap
Accessories:
SPECIFICATIONS
Label Colour Code
Blue
Black
Red
Form No. 95C-10920