Download Print this page

Honeywell 2000 Series Product Data

Electronic temperature sensors

Advertisement

C7031B,D,G,J
C7041B,C,D,F,J,K,P,R
Series 2000 Electronic Temperature Sensors
C7031B,
C7041B,C
C7031D,
C7041D
C7041R
C7031J,
C7041J

APPLICATION

The Series 2000 C7031, C7041 Electronic Temperature
Sensors are designed for use with electronic controllers in
domestic or commercial heating and cooling systems.

FEATURES

• C7031D, C7041D for immersion mounting sense water
temperature.
• C7031G, C7041F sense outdoor air temperature and
C7031G,
are weatherproof for outdoor use (knockouts allow for
C7041F
1/2 in. conduit connection).
• C7031J, C7041J,R sense average duct air temperature.
• C7031B, C7041B,C sense duct air temperature.
• C7041K with strap-on mounting senses water
temperature.
C7041P
• C7041P senses air temperature.
• Solid state components not affected by dust or dirt.

SPECIFICATIONS

Compatability: Use Series 2000 C7031, C7041 Temperature
Sensors with Excel 10, 15, 80, 100, and 500 controllers.
Series 2000 C7031B,D,G,J sensors are compatible with
various Honeywell controllers. The C7031G2014 is
compatible with the T7350 Commercial Thermostat.
C7041K
Dimensions: See Fig. 1 through 9.
Sensor Accuracy: ±0.36°F at 77°F (±0.2°C at 25°C) for 20K
ohm NTC sensors.
Accessories:
32006523-001 20K Probe: to allow replacement of old style
C7031D1062-1 with non-threaded well.
50001774-001 Stainless Steel 304 Well Assembly: 1/2 in.
external and internal NPT threading. Use with C7031D/
C7041D.
50001775-001 Well Adapter: Used with C7031D/C7041D to
allow threading sensor into previously-installed Series 1000
32005960-001 Well.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring ...............................................................................
Operation and Checkout ..................................................
PRODUCT DATA
Contents
1
1
1
2
5
8
8
Put UPC Code Here
63-2590-3

Advertisement

loading

Summary of Contents for Honeywell 2000 Series

  • Page 1: Table Of Contents

    Compatability: Use Series 2000 C7031, C7041 Temperature Sensors with Excel 10, 15, 80, 100, and 500 controllers. Series 2000 C7031B,D,G,J sensors are compatible with C7031J, various Honeywell controllers. The C7031G2014 is C7041J compatible with the T7350 Commercial Thermostat. C7041K Dimensions: See Fig. 1 through 9.
  • Page 2: Ordering Information

    If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care...
  • Page 3 C7031B,D,G,J C7041B,C,D,F,J,K,P,R SERIES 2000 ELECTRONIC TEMPERATURE SENSORS C7031B: 5-11/16 (145) C7041B: 11-5/8 (295) 1-13/16 C7041C: 17-5/8 (448) (46) 1-11/16 7/16 (12) (43) 5.75 ± 0.25 (146) 1/8 INCH NPSM STRAIGHT FOAM PAD THREADS (70) 1/8 NPSM (3) [8] 1/2 INCH CONDUIT 1-59/64 KNOCKOUTS...
  • Page 4 C7031B,D,G,J C7041B,C,D,F,J,K,P,R SERIES 2000 ELECTRONIC TEMPERATURE SENSORS 1-11/16 (43) 6-11/16 (170) 1-11/16 5 (127) 2-5/16 (43) (59) 1/2 NPSM (13) 4-3/16 (107) (70) M22596 Fig. 6. C7031D, C7041D dimensions in in. (mm) 1-11/16 (43) 1-13/16 7/16 (12) 3-7/8 (99) (46) 1-11/16 15/16 2-5/16...
  • Page 5: Installation

    C7031B,D,G,J C7041B,C,D,F,J,K,P,R SERIES 2000 ELECTRONIC TEMPERATURE SENSORS 4-3/16 (107) 1-1/2 (38) 2-5/16 1-1/2 9/16 (14) (59) (38) 7-1/8 (182) 5 (127) 1-11/16 1-1/4 (43) (32) 2-5/16 (59) 4-3/16 (70) (107) COPPER PLATE MAXIMUM PIPE DIAMETER SHOWN. FOAM PAD MINIMUM PIPE DIAMETER: 1-5/8 (41) M22134 Fig.
  • Page 6 C7031B,D,G,J C7041B,C,D,F,J,K,P,R SERIES 2000 ELECTRONIC TEMPERATURE SENSORS Duct Mounting The C7031B, C7031J, C7041B,C,J can be mounted in a duct SENSOR SENSING ELEMENTS (4) to sense air temperature. IMPORTANT Select a spot for the sensor where it will be exposed to average duct air temperature. Avoid locations where stratification can cause sensing errors.
  • Page 7 Mount the C7031D/C7041D into the well: materials. NOTE: Mounting using previously installed Honeywell The locking nut can be used to secure the probe. See Fig. 17. wells (part no.: 32005960-001) requires an adapter (part no.: 50001775-001).
  • Page 8: Wiring

    Operation WALL The C7041 Temperature Sensors are designed for use with XL500, XL100, XL50, XL15, XL10, and Honeywell LCBS Controllers or any controller requiring 20K ohm NTC non-linear input. As the temperature at the C7041 Sensor increases, the resistance of the sensor decreases, causing the controller to operate and offset the temperature change.

This manual is also suitable for:

C7031dC7031bC7031gC7041bC7031jC7041c ... Show all