Function
3 .2 .6 Test period t

for TC 4

P
The sensitivity of the tightness control TC can be ad-
justed by adapting the test period t
system. The longer the test period t
sensitivity of the TC. The longer the test period, the
smaller the leakage rate at which a safety shut-down/
fault lock-out is triggered.
The test period is set using the second jumper (on the
right in the picture).
The test period t
can be adjusted in intervals:
P
TC 410-1: 10 s to max. 60 s,
10 s = factory setting,
60 s = without jumper.
TC 410-10: 100 s to max. 600 s,
100 s = factory setting,
600 s = without jumper.
TC · Edition 08.17
for each individual
P
, the greater the
P
The required test period t
Q
= max. flow rate [m
max.
Q
= leakage rate [l/h] = Q
L
see page 35 (Leakage rate Q
p
= inlet pressure [mbar]
u
V
= test volume [l], see page 34 (Test volume V
P
for TC 1, TC 2, TC 3, TC 4)
Converting units, see www.adlatus.org.
(
p
[mbar] x V
u
t
[s] = 4 x
P
Q
[l/h]
L
3 .2 . 7 Calculation example for t
See Calculating test period t
is calculated from:
P
3
/h]
3
[m
/h] x 0.1%,
max.
)
L
)
[l]
P
  + 1 s
P
of tightness control TC 4.
P
P
33