Honeywell Accenta Series Engineer's Manual page 43

Table of Contents

Advertisement

Accenta/Optima Engineer's Manual
5 = Exit Time
This is the time allowed to leave the premises via the exit route before the system sets. The programmable
range is 00-99 seconds. The actual time is multiplied by 10.
If the Exit Time is interrupted within the last 10 seconds, then the Exit Time will restart at 10 seconds after
the interruption has cleared.
00 = 5 seconds
01 = 10 seconds
03 = 30 seconds
99 = 990 seconds (16.5 minutes)
The default is 30 seconds.
LCD Keypad:
While in Engineer program mode, to set the Exit Time,
Press [PROG] to give a choice of programs or press
[up arrow] until P>Set Up Programs is displayed then
press [SET].
Select program 1, 2 or 3.
The first screen to appear is Program Edit Used Zones.
Press [5] to enter into Exit Time edit. The Exit Time
can now be changed.
Enter a [2-digit number] from 00 to 99.
Press [SET] to accept change or [RESET] to cancel.
Press [RESET] twice to leave menu.
LED Keypad:
While in Engineer program mode, to set the Exit Time,
Press [PROG] to give a choice of programs.LED's 1,
2 and 3 are flashing.
Select program 1, 2 or 3. If program 2 is selected,
LED 2 is ON.
Select [4] to enter into Exit Time edit. The Exit
Time can now be changed. LED 2 is ON.
Enter a [2-digit number] from 00 to 99. LED 2 is
ON.
Press [SET] to accept change or [RESET] to cancel.
Press [RESET] twice to leave menu.
Programs (cont'd)
P>Select
P>Select
P>Select
P>Select
P>Select
1 2 or 3
1 2 or 3
1 2 or 3
1 2 or 3
1 2 or 3
P>Program Edit
P>Program Edit
P>Program Edit
P>Program Edit
P>Program Edit
P>Program Edit
P>Program Edit
P>Program Edit
P>Program Edit
P>Program Edit
Exit Time? --
Exit Time? --
Exit Time? --
Exit Time? --
Exit Time? --
[2-digit number] then [SET] or [RESET]
P>Program Edit
P>Program Edit
P>Program Edit
P>Program Edit
P>Program Edit
Exit Time
Exit Time
Exit Time
Exit Time
Exit Time
P>Set Up
P>Set Up
P>Set Up
P>Set Up
P>Set Up
[2-digit number] then [SET] or [RESET]
39
[PROG]
Program
Program
Program
Program
Program
[Number]
Used Zones
Used Zones
Used Zones
Used Zones
Used Zones
[4]
[RESET]
Programs
Programs
Programs
Programs
Programs
[PROG]
1
2
3
4
5
6
[2]
3
4
5
6
1
2
[4]
1
2
3
4
5
6
3
4
5
6
1
2
[RESET]
1
2
3
4
5
6
8
7
7
8
8
7
7
8
7
8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Optima series

Table of Contents