Power
?
yellow and permanently lit?
! Safety interlock input signal is interrupted, no
1
2
voltage at terminal 5. The tightness test is still
being carried out. No enable signal is issued to
the automatic burner control unit.
• Check safety interlocks.
! Fuse F2 defective.
• Replace fuse F2, see page 9 (Replacing the
fuse).
Power
?
yellow and flashing?
1
! Permanent remote reset. The remote reset signal
2
has been active for more than 10 s.
• The warning signal is cancelled once the remote
reset signal to terminal 11 has been removed.
Power
?
red and permanently lit?
! Incorrect jumper/DIP switch setting.
1
2
• Correct jumper and DIP switch setting, see
pages  7 (Setting measurement time tM)
and  6 (Setting the test instant). Then press
the reset button.
! Internal error.
• Remove the unit and return it to the manufacturer
for inspection.
Power
?
red and flashing?
1
! Too frequent burner start commands. The TC
2
performs a fault lock-out. The start commands
are limited to 5 x in 15 minutes.
▷ As long as this limit is not exceeded, another
start-up attempt is possible after three further
minutes. If a tightness test is completed, the
counter which limits the number of start com-
mands is reset.
• Then press the reset button.
! Too many remote resets. More than 5 resets
have been conducted within the last 15 minutes,
either automatically or manually.
! Consecutive fault caused by a previous fault
whose actual cause has not been remedied.
• Pay attention to previous fault messages.
Power
• Remedy cause. Then press the reset button.
Power
1
?
or
red and permanently lit?
2
1
! The valve is leaking. The TC performs a fault
2
lock-out.
• Replace the valve.
! Wiring of the TC to the valves is faulty.
• Start the program and observe the interspace
pressure p
. The pressure must change during
z
the TEST phase. Check the wiring.
! Inlet pressure p
< 10 mbar.
u
• Provide the min. inlet pressure of 10 mbar.
! Interspace pressure p
cannot be reduced.
z
• The volume downstream of the valve on the
burner side must be 5 times higher than the
volume between the valves and atmospheric
pressure must prevail.
! The measurement time t
• Readjust t
, see page  7 (Setting measure-
Power
M
ment time tM).
Power
1
?
and
2
1
! During the tightness test, the TC has determined
2
that inlet valve 1 and outlet valve 2 have been
reversed (fault lock-out).
• Check the wiring. Then press the reset button.
? No LED lit even though mains voltage ap-
plied?
! Fuse F1 defective.
• Replace fuse F1, see page 9 (Replacing the
fuse).

Replacing the fuse

▷ The fuses F1 and F2 can be removed for in-
spection.
▷ Insert a screwdriver into the opening in the con-
tact guard to prise out the fuse.
 Disconnect the TC from the electrical power
supply.
▷ Before opening the unit, the fitter should ground
himself.
 Unscrew the housing cover.
 Remove fuse F1 or F2.
4 Check function of fuse.
5 Replace the defective fuse.
▷ When replacing the fuse, use only the approved
fuse type, see page 10 (Technical data).
▷ Restart the TC, see page 8 (Commissioning).

Maintenance

Tightness controls TC require little servicing. We rec-
ommend carrying out a function check once a year
or twice a year in the case of biogas.