Siemens SIMATIC S5 Equipment Manual page 45

Digital position decoder ip 241 with fb 156/1 57 158
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

2.6
GeneraI Interrupt Processing with S5-135U
A separate hardware interrupt line is allocated to each CPU slot (IRA to IRD).
The 1P triggers an interrupt by activating the interrupt line (i.e., by outputting a low–signal)
In the corresponding CPU a jump to interrupt 062 is effected (for more details see Equipment
Manual for the S5–135U).
slot
CPU 1 CPU 2 CPU 3 CPU 4 Peripherals
For interrupt processing the 1P must be inserted into a slot with interrupt line
(slots 43 to 131). See section 8.8.
Interrupts are not possible in the expansion unit unless lines exist there (e.g.,
ER 701–3 or EG 186U) and the devices are connected via interface IM 307/317.
. Setting for 1P 241 without interrupt processing
DIP switch S1: IRA to IRD : OPEN
DIP switch S2: All switches OPEN
Setting for one 1P 241 with interrupt processing
One of the lines IRA to IRD must be selected with DIP switch S1.
The switches for the remaining lines must be openad!
Setting for two to eight 1P 241s with interrupt processing
One of the lines IRA to IRD must be selected with DIP switch S1; (the same line for all master
and slave modules).
The switches for the remaining lines must be opened!
The individual modules must be set in accordance with the Master/Slave principle
(see section 2.4).
If several IPs are used on one interrupt line, the triggerin 1P can be recognized by
evaluating the peripheral byte. For more details see the quipment Manual for your
programmable controller.
Evaluation of the peripheral byte O is only possible if the module is addressed in the
P–area.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Allocation of IRA to IRD
via DIP switch S1
Interrupt
DIP switch S1
lines
IRA
S1 .6
S1 .8
Operating Instruction
CPU 1
CPU 2
CPU 3
CPU 4
2 – 11