Use Of Check Valves; Connection Diagram For A Double Pipe System - Honeywell F-BO-AFE70 Series Installation, Connection, Commissioning, Maintenance

Automatic purging units for aspirating detectors
Table of Contents

Advertisement

User Manual Series F-BO-AFE70
8.2.3

Use of check valves

It is recommended that a check valve should be mounted at the end of every branch of the pipe sys-
tem. Mounting a check valve ensures that the dirt particles and ice particles will be blown out of
the pipe in the best possible way. In addition, the check valve also serves to limit the pressure in the
piping, thereby relieving the aspiration holes during the Purging process. Ideally, the opening over-
pressure of the check valve should be around 25kPa (0.25bar).
The cleaning of the aspiration holes is also ensured without a check valve, but it is not ensured
that the dirt particles will be blown out along the whole length of the pipe in the best possible
way.
8.2.4

Connection diagram for a double pipe system

The following figure shows the schematic connection of the components needed for purging two
separate pipe systems of an aspirating smoke detector.
Fig. 8:
Aspirating smoke detector with two separate pipe systems. As a supplement to Fig. 2 (page 10),
electrical connection cables are not shown here in order to provide a clearer overview.
A ... Aspirating smoke detector with two separate pipe systems
B ... F-BO-AFE70 for the first pipe system
C ... Filter before the Purging unit of pipe system 1 (option)
D ... F-BO-AFE70 for the second pipe system
E ... Filter before the Purging unit of pipe system 2 (option)
If the aspirating smoke detector used has separate fault outputs for each individual pipe network,
the Purging units can be actuated individually. As a result, the pipes can also be purged independ-
ently of each other in the event of a fault.
If the aspirating smoke detector used does not have separate fault outputs for each individual pipe
network, but has only one common fault output for all pipe networks, the Purging units must be
connected and operated in the master-slave mode. In this case, the pipes will always be purged
together.
I56-4252-010
D200-104-00
Chapter 8 • Mounting and connection of pneumatic components
27