Honeywell IFP-300 Basic Operating Instructions page 2

Hide thumbs Also See for IFP-300:

Advertisement

Check Detector
Sensitivity
Set Time and Date
Enable / Disable a Point
View Event History
For Service Call:
Press ENTER to access Main Menu.
1.
Press 2 for Point Status.
2.
From the list that displays, select the SLC module where the point you want to view is
3.
located.
The fourth line of the display shows the sensitivity status. "NORMAL" means the
4.
detector is in compliance with NFPA 72.
"CAL MAINT" means the detector is in compliance with NFPA 72 but maintenance should
be performed soon.
"CAL TRBLE" means the detector is not in compliance with NFPA 72.
Press ENTER to access Main Menu.
1.
Press 4 to select Set Time & Date. Enter a code if prompted
2.
Make changes in the fields on the screen as necessary.
3.
When the time and date are correct, press ENTER.
4.
Press ENTER to access Main Menu.
1.
Press 2 to select Point Functions.
2.
Press 1 for Disable / Enable Pt
3.
Press 7 for Disable / Enable Pt.
4.
Use the Up or Down button to move through the list. Then press ENTER to select the
5.
module where the point you want to disable/enable is located
Enter the point or circuit number that you want to disable/enable.
6.
Press the right arrow key to toggle between NORMAL (enable) or DISABLE.
7.
From the Program Menu.
1.
Press 3 to select Event History.
2.
Press the Up or Downbutton to view events in the history buffer.
3.