Section 3
630 series overview
3.2.4.2
3.2.4.3
24
Table 11:
Alarm indications
LED state
Description
Off
Normal operation. All activation signals are off.
On
Follow-S sequence: The activation signal is on.
LatchedColl-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
LatchedAck-F-S sequence: The indication has been acknowledged, but the
activation signal is still on.
LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
LatchedReset-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
Flashing
Follow-F sequence: The activation signal is on.
LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
LatchedAck-S-F sequence: The indication has been acknowledged, but the
activation signal is still on.

Parameter management

The LHMI is used to access the relay parameters. Three types of parameters can be
read and written.
Numerical values
String values
Enumerated values
Numerical values are presented either in integer or in decimal format with minimum
and maximum values. Character strings can be edited character by character.
Enumerated values have a predefined set of selectable values.

Front communication

The RJ-45 port in the LHMI enables front communication.
The green uplink LED on the left is lit when the cable is successfully connected
to the port.
1MRS756509 E
630 series
Operation Manual