Honeywell CIPer 50 Installation & Commissioning Instructions page 7

Hide thumbs Also See for CIPer 50:
Table of Contents

Advertisement

Fig. 5. Configuring the RS232 Interface in WEBs N4
USB 2.0 Host Interface
Via its USB 2.0 Host interface, the CIPer Model 50 con-
troller can be connected to, e.g., the IF-LON2 External
Interface Adapter and thus to L
200 mA, high speed. See also section "LonWorks
Communications" on pg. 33.
USB 2.0 HOST INTERFACE
Fig. 6. USB 2.0 Host interface
USB 2.0 Device Interface
All models of the CIPer Model 50 controller are equipped
with a USB 2.0 Device Interface at the front. This interface
is for connection to WEBs N4 and web browsers, or 3
party touch panels.
CIPer MODEL 50 CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
W
networks. Max.
ON
ORKS
rd
-
Fig. 7. USB 2.0 Device Interface
A standard USB type-B connector can be inserted into this
USB 2.0 Device Interface. This USB 2.0 Device Interface is
the recommended interface for connection to WEBs N4.
Ethernet / RJ45 Sockets
The CIPer Model 50 controller is equipped with two
Ethernet / RJ45 sockets, each featuring two LEDs.
ETHERNET / RJ45 SOCKETS
Fig. 8. Ethernet / RJ45 sockets
The two Ethernet / RJ45 sockets are 10/100-Mbit/s
Ethernet interfaces permitting communication (as per
IEEEC 802.3) on any supported IP network, e.g.: BACnet
(IP), FOX, etc.
RIGHT (YELLOW) LED
LIT CONTINUOUSLY = "100 Mbaud"
DARK
INTER-
FACE 1
LEFT (GREEN) LED
LIT CONTINUOUSLY =
DARK
Fig. 9. Ethernet / RJ45 sockets
NOTE: The Ethernet / RJ45 sockets are usually earth-
grounded. For additional information, see also
"Appendix 1: Earth Grounding" on pg. 46.
The two Ethernet interfaces can be used in either of two
different ways (the corresponding configuration is done in
WEBs N4):
7
INTER-
INTER-
FACE 1
FACE 2
=
"10 Mbaud"
INTER-
FACE 2
"
LINK ACTIVE
"
= "
LINK INACTIVE
"
31-00233EFS-01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents