Honeywell H7012A Series Manual page 4

Room humidity sensor/ combined room humidity/temperature sensor

Advertisement

H7012A,B Room Humidity / Temperature Sensor
Mounting and Installation Advice:
• Mount these units at the inside wall of the room to be
heated or air conditioned, away from doors, windows
and heat sources.
• Do not mount in niches, book shelves, behind cabinets
or curtains or where it could be exposed to solar
radiation.
• Seal the conduit opening to avoid false measurement
due to draught from the conduit.
• Provide sufficient air circulation.
Offset due to wire resistance per 10m distance from sensor
to controller:
Type of wire
Pt 1000
2
0.5mm
0.18°C (0.324°F)
(AWG20)
2
1.0mm
0.09°C (0.162°F)
(AWG17)
2
1.5mm
0.06°C (0.108°F)
(AWG15)
Wiring connection
24V
1
24V
2
3
Pt 1000/NTC/
BALCO 500
4
0...1V
5
0...10V
6
7
COM = 24V
8
9
10
Honeywell Regelsysteme GmbH
Honeywellstr. 2-6
D-63477 Maintal
Tel. (0 61 81) 401-1
Fax (0 61 81) 4 54 56
Subject to change without notice. Printed in Germany.
EN0C-0610 0398R3-MA
Temperature offset
BALCO 500
0.3°C (0.54°F)
0.15°C (0.27°F)
negligible
0.1°C (0.1°F)
POWER SUPPLY
TEMPERATURE SENSOR
REL. HUMIDITY SENSOR
Fig. 4 Installation
Use shielded wiring in areas with high EMI.
Keep 15cm (5.9'') minimum distance between
sensor lines and 230Vac power lines.
Use two transformers: one for sensors and
actuators and one for the controller (see Fig. 3).
Wiring run
NTC
Sensor to controller
Manufacturing location is certified according to
NOTE
CAUTION
Maximum length
200m (660ft)
1 2 3 4
5
6 7
8 9 10

DIN
EN ISO 9001