1.
With outside poles open, loosen
adjus
tment
plate (10) of center pole on crossbar
(9)
by
freeing-
.;bolt locking tab and loosening bolts (11).
_2.
.
If
center-pole wipe or overlap is to be
increased, move the adjustment plate to the left;
if
it is
to
be decreased, move
it
to the right.
3.
After proper adjustment is made, tighten
adjus
tment plate bolts until plate is
snug.
Then
tap adjustment plate in such a way
as
to bring
lower
edge of slot in plate to bear against bolt.
Tighten
bolt until
lockwasher is
fully
compressed.
Then
form locking tabs over bolt heads so that
bolts are securely
held
in place.
NOTE:
If
the
above adjustment has been made,
it
is necessary
to-recheck the outer-pole
wipe.
If
this is outside the prescribed limits, correct
as described
in
POLE UNIT ASSEMBLY.
4.
If
proper wipe cannot be obtained within
the range of the
adjus
tment described above, it
will
be necessary to obtain further adjustment by
_means of the
vertical
-shims (14) provided for the
purpose.
In order
to
accomplish this, proceed
as follows:
·
a.
Separate the front -frame from the back
frame (see
SEPARATION OF FRONT AND REAR
FRAMES).
·
b.
Loosen -screw (13) and remove bolt
(15).
c.
Remove vertical
shims
(14) to decrease
.
wipe; add to increase
•.
d.
Replace bolt
(i5)
and·
tighten screw
(13).
e.
Reassemble front and back
frame.
Adiusting
Center-pole
Open
Contact
G_ap
(Fig. 17}
Improper
open contact gap of
the
center
pole
may be adjusted by -the following
procedur
e.
1.
Loosen screw (13) and bolt (15).
2.
If
gap i
s
to
be increased,
horizontal
shims
-
(14) should be
remove·
d
,
.
If
it is
to
be
decreased,
they should be added. Shims may
be removed by
sliding them to the front of the breaker.
They
are ·slotted for
easy
r_
e moval.
(Effect of
this ad-
j1.:1stmen~
on contact wipe and overlap is negligible.)
3.
Tighten hardware.
Contact
Replacement
·
-
Stationary Contacts
(Fig.
17)
-
.
1:
Remove arc quencher (see ARC QUENCHER).
2.
Remove
s
crew (5) from braid.
3.
Drift out pin (4) and remove contacts.
4.
Reassemble
in
reverse order with
new
Low Voltage Power Circuit Breakers GEK-7303
contacts.
5.
Check contact overlap anc;l wipe, and re-
adjust
if
necessary (see above).
Movable Contacts
(Fig.
17)
1.
Remove
arc quencher (see ARC
_
QUEN-
CHER).
2.
Remove
tru-arc
r etainers on right side of
pins
(7)
and
(16).
3.
Drift pins
(7)
and (16) to the.left far enough
to free movable
contacts.
4
.
Reassemble in reverse order with new
contacts.
5.
Check contact overlap and wipe and
re-
adjust
if
necessary (see above}.
,----
-- - -
9
,-------a
- - -
--
7
,--- -
--
6
r----
-
-
5
,----
4
Fig.
18
(0133C9020) Auxiliary
.
switc~ linkag-e
·
-standard
breaker
-
AUXILIARY SWITCH
AK BREAKERS
(Fig, 18)
The auxiliary switch is used to make and break
various control circuits as the circuit breaker
is
opened and
closed,
The auxiliary switch
is
mounted
on
the left
side of
thefrontframe.
As the crossbar
(4)
moves,
with the contacts, to the open or closed
position
it
operates a triangular link (6) through
an
operating
rod·
(5).
The triangular
link
rotates
the operating
shaft
(8)
of the auxiliary switch,
which,
through
cams
located
on this shaft, opens and closes
the auxiliary switch
contacts.
The_
top terminals
of
the switch are
"a"-
contacts (open
when
the
breaker
is
open)
and the bottom terminals
are
"b"
contacts (closed
when U1e
broako;r
is
open).
Repl~mmenl
(Fig.
18)
1.
Disconnect all leads to auxiliary switch.