Generic Controller I/O Layout. See Wiring Diagram for application specific details.
Control Applications
6750, 6756
Product Description
The Siemens Venturi Air Valve is a pre-packaged,
easy to install airflow measurement and control
solution. It provides stable and precise airflow
control of room supply, room general exhaust or
fume hood exhaust.
These instructions explain how to field install or
replace the BACnet Laboratory Controller Module
LCM.
This BACnet LCM-OAVS VAV Room Pressurization
Controller with HW Reheat and Two Fast-acting
Venturi Air Valves — One Exhaust, One Supply
features VAV control of a laboratory room with one
supply duct, one exhaust duct, and up to six Fume
Hoods. It uses fast-acting electronic actuators
(shipped separately) to control the supply and
exhaust Venturi air valves.
Item No. 570-114 Rev. CA
Installation Instructions
This controller is built on a BACnet Programmable
TEC (PTEC) platform that supports up to two
Offboard AVS signals; however, Onboard AVS
transducers are not supported. Offboard Air
Module(s) (OAM) house AVS transducers and send
signals to the AVS input(s) on the LCM OAVS
board.
The LCM can operate stand-alone, with a field
panel, or as part of a network.
Product Numbers
Venturi Air Valve for Critical Environments
See the
Technical Specification Sheet
Configuration and Sizing
section of InfoLink.
BACnet LCM-OAVS with HW Reheat
and Two Venturi Air Valves — One
Exhaust, One Supply Applications 6750
(RTS) 6756 (BTU)
This controller requires Offboard Air
Module(s) (ordered and shipped
separately
Document No. 570-114
October 26, 2016
(149-425) or
in the Critical Environments
570-804PA
Page 1 of 8

Advertisement

loading

Summary of Contents for Siemens LCM-OAVS 570-804PA

  • Page 1 Product Description signals to the AVS input(s) on the LCM OAVS board. The Siemens Venturi Air Valve is a pre-packaged, easy to install airflow measurement and control The LCM can operate stand-alone, with a field solution. It provides stable and precise airflow panel, or as part of a network.
  • Page 2 Offboard Air Module – two required, 550-819B Prerequisites order separately Wiring conforms to NEC and local codes and  Siemens fast-acting Lab Electronic GNP191.1U regulations. For further information, see the Actuator(s) – order and ship separately) Wiring Guidelines Manual (125-3002).
  • Page 3 For each Fast Acting Lab Electronic Actuator, verify that the switches are set as shown in Switch Settings for the Fast Acting Figure Lab Electronic Actuator Dimensions. Supply Exhaust Switch Settings for the Fast Acting Lab Electronic Actuator. Siemens Industry, Inc. Page 3 of 8...
  • Page 4: Wiring Diagrams

    AC neutral to the DC common will result in equipment damage. of the PTEC/TEC AO being used to control the actuator. Wiring for AI with a 4 to 20 mA Sensor. 24 Vac Modulating Control. Page 4 of 8 Siemens Industry, Inc.
  • Page 5 • DC power requirements • Separate transformers used to power the load (for example, part number 540-147, Terminal Equipment Controller Relay Module) NOTE: Thermistor inputs are 10K (default) or 100K software selectable (AI Siemens Industry, Inc. Page 5 of 8...
  • Page 6 Document No. 570-114 Installation Instructions October 26, 2016 BACnet LCM-OAVS with Hot Water Reheat and Two Venturi Air Valves (One Exhaust, One Supply) -- Application 6750 Wiring Diagram. Page 6 of 8 Siemens Industry, Inc.
  • Page 7 Document No. 570-114 Installation Instructions October 26, 2016 BACnet LCM-OAVS with Hot Water Reheat, BTU Compensation, Two Venturi Air Valves (One Exhaust, One Supply) -- Application 6756 Wiring Diagram. Siemens Industry, Inc. Page 7 of 8...
  • Page 8: Cyber Security Disclaimer

    Document No. 570-114 Installation Instructions October 26, 2016 Cyber security disclaimer Products, solutions and services from Siemens include security functions to ensure the secure operation of building automation and control, fire safety, security management, and physical security systems. The security...