PROCEDURES AND SETTINGS BEFORE SYSTEM
OPERATION

6.1.2 Replacement procedure of the module

Figure 6.2 shows the replacement procedure of the safety remote I/O module.
For the function differences between managing and not managing the production
information, refer to CHAPTER 5(1).
For the connection between the safety CPU module and GX Developer, refer to the "GX
Developer Version 8 Operating Manual (Safety Programmable Controller)".
Confirmation of new module operation
Execute the self-loopback test of new safety remote I/O module.
For the self-loopback test, refer to Section 6.4.
Switch setting of new module
Save the settings for the link ID, station number and transmission speed setting
switch of the new safety remote I/O module to the nonvolatile memory inside the
module.
For the switch setting, refer to Section 6.6.
Change to TEST MODE
Change the safety CPU operation mode to TEST MODE using GX Developer.
For changing to TEST MODE of the safety CPU module, refer to the "QSCPU User's
Manual (Function Explanation, Program Fundamentals)".
Production information change
1) Change the production information of the safety remote I/O module to that of
the new safety remote I/O module using GX Developer.
2) Write the parameters changed by GX Developer to the safety CPU module.
(The parameters are written to the safety remote I/O module via the safety
master module at data link .)
For writing parameters to the safety CPU module, refer to the "GX Developer
Version 8 Operating Manual".
Setting reflection
Make the set production information valid by performing the reset operation of the
safety CPU module or turning the power OFF
Power-off
Turn OFF the power supply of the safety remote I/O module.
6
- 3
6.1 Procedures and Settings before System Operation
6.1.2 Replacement procedure of the module
in Figure 6.2 indicates the operation for managing the production information.