Class B Supervised Wiring; Class B Output Notification Circuits; Releasing Operations - Honeywell 5496 Installation And Operation Manual

Intelligent power module
Hide thumbs Also See for 5496:
Table of Contents

Advertisement

Model 5496 Intelligent Power Module Installation and Operation Manual
3.4.2

Class B Supervised Wiring

Figure 3-6 shows how to wire for Class B output supervision. Use in/out wiring
methods for proper supervision. Refer to Section 4 for notification appliances that
must be used with the 5496.

Class B Output Notification Circuits

Figure 3-6 shows four, 1.5 amp devices wired as Class B circuits.
Place a 4.7k ohm EOL resistor (provided) at the end of each circuit to enable
supervision when using all outputs as Class B notification appliance circuits. The 4.7k
EOLs must be wired to the terminals whether or not you are using all output
terminals.
Figure 3-6 Regulated Class B Supervised Input/Output Connections
3.4.3

Releasing Operations

Approved releasing solenoids are list in Table 3-1
with smoke verification zones. There must be at least two automatic detection
devices in each protected space. Spacing must be reduced to 0.7 times the linear
spacing in accordance with NFPA 72.
Manufacturer
Asco
T8210A107
8210G207
Table 3-1: Approved Releasing Solenoids
Part Number
3-6
Power Limited
1.5Ω max
Do not mix cross alarming zones
.
Rating
Current
24 VDC
3A max
24 VDC
3A max
151276-L8
Freq
0 Hz
0 Hz