APPLICATION
This document covers the mounting and wiring of the
NPB-LON option card in a WEB-201, CP-201 or
WebStat™ series controller.
Table 1. NPB-LON Option Description.
Description
FTT-10A LON
(LonWorks) adapter
with 2-position
removable screw-
terminal connector plug.
For related mounting and wiring details, please see the
Mounting and Wiring Instructions document, form no.
95-7722.
CONTENTS
Included in this package are the following items:
• An NPB-LON option card, along with connector end
plate.
• One 2-position terminal plug, for wiring to an FTT-10
®
LonWorks
network.
• This NPB-LON Installation Instructions.
MATERIAL AND TOOLS REQUIRED
The following tools and supplies may be required for
installation:
• #2 phillips screwdriver: use to install the NPB-LON.
• Small flat-blade screwdriver: used for making wiring
connections to the FTT-10 LonWorks network.
Notes
®
Up to 2 LON
option cards
may be installed.
• If one Lon option, it
operates as LON1,
regardless of slot.
• If two LON options, LON1
is Option slot 1 and LON2
is Option slot 2.
See Fig. 2 for location of
option slots.
INSTALLATION INSTRUCTIONS
Fig. 1. NPB-LON Option.
MOUNTING
WARNING
Power to the controller must be off when
installing or removing option cards or
damage will occur! Also, be very careful to
plug any option card into its connector
properly (pins aligned).
Mount the NPB-LON option card in either of the option
card slots of the controller as available. See the notes in
Table 1 about LON adapter software assignments if
installing two NPB-LON option cards.
Mounting NPB-LON option card on a
controller
1. Remove power — See the above warning.
2. Remove the cover. To do this press the four tabs
on both ends of the unit and lift the cover off.
NOTE: If accessory modules are plugged into the con-
troller, they may need to be slid away from the
unit to get to the cover tabs.
3. Remove the battery and bracket assembly by tak-
ing out the four screws holding it in place and set
them aside for later. Unplug the battery from the
connector on the controller (See Fig. 2).
RX TX
LON
M23324
62-0263

Advertisement

loading

Summary of Contents for Honeywell NPB-LON

  • Page 1 • An NPB-LON option card, along with connector end plate. Mount the NPB-LON option card in either of the option • One 2-position terminal plug, for wiring to an FTT-10 card slots of the controller as available. See the notes in ®...
  • Page 2 ONEYWELL NTERNATIONAL By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.