Input Power Connections - ABB ACQ550-x1-06A6-2 User Manual

Acq550 series, acq550-u1 drives (1-200 hp)
Table of Contents

Advertisement

ACQ550-U1 User's Manual

Input power connections

WARNING! Do not operate the drive outside the nominal input line voltage range.
Overvoltage can result in permanent damage to the drive.
Input power specifications
Prospective short-
circuit current
Fundamental power
factor (cos phi
Cable temperature
Disconnecting device for isolation
Install a hand-operated input disconnecting device (disconnecting means) between
the AC power source and the drive. The disconnecting device must be of a type that
can be locked to the open position for installation and maintenance work.
• Europe: To meet the European Union Directives, according to standard
EN 60204-1, Safety of Machinery, the disconnecting device must be one of the
following types:
– a switch-disconnector of utilization category AC-23B (EN 60947-3)
– a disconnector having an auxiliary contact that in all cases causes switching
– a circuit breaker suitable for isolation in accordance with EN 60947-2.
• Other regions: The disconnecting device must conform to the applicable safety
regulations.
Fuses
Branch circuit protection must be provided by the end user and sized per national
and local electric codes. The following tables provide fuse recommendations for
short circuit protection on the drive's input power.
The rated fuse currents given in the tables are the maximums for the
mentioned fuse types. If smaller fuse ratings are used, check that the fuse rms
current rating is larger than the input current.
Input power (mains) connection specifications
208/220/230/240 V AC 3-phase (or 1-phase) -15%...+10% for
ACQ550-x1-xxxx-2.
Voltage (U
)
380/400/415/440/460/480 V AC 3-phase -15%...+10% for ACQ550-x1-
1
xxxx-4.
500/525/575/600 V AC 3-phase -15%...+10% for ACQ550-U1-xxxx-6.
Maximum allowed prospective short-circuit current in the supply is 100 kA
providing that the input power cable of the drive is protected with
(IEC 629)
appropriate fuses. US: 100 000 AIC.
Frequency
48...63 Hz
Imbalance
Max. ± 3% of nominal phase to phase input voltage
0.98 (at nominal load)
)
1
90 °C (194 °F) rating minimum
rating
devices to break the load circuit before the opening of the main contacts of the
disconnector (EN 60947-3)
271
Technical data