256
Faults that indicate conflicts in the parameter settings are listed below.
Fault
code
1000
1001
1002
1003
1004
1005
1006
1007
1008
1009
1010/
1011
1012
1013
Diagnostics
Fault name in
panel
Parameter values are inconsistent. Check for any of the following:
PAR HZRPM
• 2001
MINIMUM SPEED
• 2007
MINIMUM FREQ
• 2001
MINIMUM SPEED
(> 50).
• 2002
MAXIMUM SPEED
(> 50).
• 2007
MINIMUM FREQ
(> 50).
• 2008
MAXIMUM FREQ
(> 50).
Parameter values are inconsistent. Check for the following:
PAR PFC REF
NEG
• 2007
MINIMUM FREQ
Not used.
RESERVED
Parameter values are inconsistent. Check for any of the following:
PAR AI SCALE
• 1301
MINIMUM AI
• 1304
MINIMUM AI
Parameter values are inconsistent. Check for any of the following:
PAR AO SCALE
• 1504
MINIMUM AO
• 1510
MINIMUM AO
2
Parameter values for power control are inconsistent: Improper motor
PAR PCU
nominal kVA or motor nominal power. Check for the following:
• 1.1 < (9906
where: P
or P
N
Parameter values are inconsistent. Check for the following:
PAR EXT RO
• Extension relay module not connected and
• 1410...1412
Parameter values are inconsistent. Check for and correct:
PAR FIELDBUS
MISSING
• A parameter is set for fieldbus control (e.g. 1001
(
COMM
Parameter values are inconsistent – 9904
PAR PFC MODE
(
:
SCALAR
FREQ
1
Parameter values for power control are inconsistent: Improper motor
PAR PCU
nominal frequency or speed. Check for both of the following:
• 1 < (60 · 9907
• 0.8 < 9908
(120 · 9907
Not used.
RESERVED
1
IO configuration is not complete – not enough relays are parameterized to
PAR PFC IO
PFC. Or, a conflict exists between
8117
NR OF AUX MOT
2
IO configuration is not complete – the actual number of PFC motors
PAR PFC IO
(parameter 8127,
RELAY OUTPUTS
Description and recommended corrective action
> 2002
MAXIMUM SPEED
> 2008
MAXIMUM FREQ
/ 9908
MOTOR NOM SPEED
/ 9908
MOTOR NOM SPEED
/ 9907
MOTOR NOM FREQ
/ 9907
MOTOR NOM FREQ
is negative, when 8123
1 > 1302
MAXIMUM AI
2 > 1305
MAXIMUM AI
1 > 1505
MAXIMUM AO
2 > 1511
MAXIMUM AO
· 9905
MOTOR NOM CURR
= 1000 · 9909
MOTOR NOM POWER
N
= 746 · 9909
MOTOR NOM POWER
4...6 have non-zero values.
RELAY OUTPUTS
)), but 9802
COMM PROT SEL
), when 8123
PFC ENABLE
MOTOR NOM FREQ
/
MOTOR NOM SPEED
/ Motor Poles) < 0.992
MOTOR NOM FREQ
Group 14: RELAY
and parameter 8118
) does not match the PFC motors in
MOTORS
and parameter 8118
ACQ550-U1 User's Manual
.
.
is outside proper range
is outside proper range
is outside proper range
is outside proper range
is active.
PFC ENABLE
1.
2.
1.
2.
· 1.73 / P
MOTOR NOM VOLT
(if units are kW)
(if units are hp, e.g. in US)
1
EXT
COMMANDS
= 0.
must be = 3
MOTOR CTRL MODE
is activated.
/ 9908
< 16
MOTOR NOM SPEED
OUTPUTS, parameter
.
AUTOCHNG INTERV
.
AUTOCHNG INTERV
) < 3.0
N
= 10
Group 14: