ABB PST30 Installation And Maintenance Manual page 82

Pst series; pstb series
Hide thumbs Also See for PST30:
Table of Contents

Advertisement

Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com
Chapter 10
Functions
10:61 Current limit, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Curr Lim2
This parameter makes it possible to set the current limit level for the second parameter set.
Parameter text
Curr Lim2
10:62 Setting current, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./2nd Set Ie
This parameter makes it possible to set the rated motor current for the second parameter
set.
Parameter text
2 Set Ie
10:63 Start ramp, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Start Ramp3
This parameter makes it possible to set the start ramp time for the third parameter set.
Parameter text
Start Ramp3
10:64 Initial voltage, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Init Volt3
This parameter makes it possible to set the initial voltage for the third parameter set.
Parameter text
Init Volt3
10:65 Current limit, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Curr Lim3
This parameter makes it possible to set the current limit level for the third parameter set.
Parameter text
Curr Lim3
10:66 Setting current, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq. Start/3rd Seq. Param./3rd Set Ie
This parameter makes it possible to set the rated motor current for the third parameter set.
Parameter text
3rd Set le
Default value
Setting range
Description
4 x Ie
2.0...7.0xle
Second sequence, current limit
Default value
Setting range
9...1207A divided into 19
Ir
overlapping ranges
Default value
Setting range
Description
10s
1...30s, 1...120s
Third sequence, time for start ramp
Default value
Setting range
Description
30%
30...70%
Third sequence, initial voltage for start ramp
Default value
Setting range
Description
4 x Ie
2.0...7.0xle
Third sequence, current limit
Default value
Setting range
9...1207A divided into 19
Ir
overlapping ranges
Description
Second sequence, current limit
Description
Third sequence, motor rated
current
10.17
1SXU 132 021 M0201
10

Advertisement

Table of Contents
loading