The above logged event will be displayed approximately once every 10 seconds
until the problem is corrected. If the WAG IP address is altered to remove the
conflict or another device on the LAN is reconfigured to correct the problem, the
WAG power must be cycled to reset the problem reporting.
It is possible there is a shared IP address even if the user does not see it in the routing table.
Examine the configuration of all WAGs on the Ethernet LAN.
To help isolate the problem WAG, open a DOS window on a computer connected to the same
Ethernet LAN and PING the suspect IP address. Now power down each WAG individually,
performing a PING after each power removal, until the PING responses disappear.