Table 6. Installer Setup Numbers and Default Settings and Options. (Continued)
Installer
Setup
Number
(Press
key to
change)
Description
5
Number of heating
stages.
8
Number of cooling
stages (maximum for
W8635B is one).
9
Number of emergency
heat stages (only when
used with W8835 or
W8635B).
13
Adaptive Intelligent
Recovery™ (system
starts early so setpoint
is reached by start of
program period).
14
Temperature indication
scale (°F or °C)
16
Clock format
19
Fan overrun in heating
(not implemented for
gas/oil heat).
20
Fan overrun in cooling.
25
Keypad lockout.
30
Minimum deadband
between heating and
cooling.
33
Minimum off time for
cooling and compressor.
34
Maximum setpoint
range stop for heating.
35
Minimum setpoint range
stop for cooling.
T8635L MICROELECTRONIC COMMUNICATING PROGRAMMABLE THERMOSTAT
Scope
Display
Global 1, 2
Global 1, 2
Global 1
Global 0
Global 0
Global 0
Global 0
Global 0
Local
0
Global 3
Global 5
Global 90°F
(32°C).
Global 45°F
(7°C).
Default Setting
Description
Number of heating
stages found during
Automatic Discovery
mode.
Number of cooling
stages found during
Automatic Discovery
mode.
Number of
emergency heating
stages.
Adaptive Intelligent
Recovery™ is
activated.
Temperature is
indicated in °F.
12-hour clock format 1
0 seconds of fan
operation after
heating turns off.
0 seconds of fan
operation after
cooling turns off.
No lockout
Heating and cooling
setpoints can be set
no closer than 3°F
(1.5°C) to 10°F
(5 °C).
Five-minute minimum
off time for the
compressor.
Heating setpoint
range can be set no
higher than 90°F
(30°C).
Cooling setpoint
range can be set no
lower than 45°F.
11
Other Options (Press
key to change
Display
Description
0, 1, 2, 3
Select the number of
heating stages for this
application.
0, 1, 2
Select the number of
cooling stages for this
application.
0, 1, 2
Select the number of
emergency heat stages
for this application.
1
Conventional recovery
(system starts recovery
at period start time).
1
Temperature is indicated
in °C.
24-hour clock format.
1
90 seconds of fan
operation after heating
turns off.
1
90 seconds of fan
operation after cooling
turns off.
1
1—Locks out all except
i, run, dst, and set
current day/time.
2—Locks out all except i,
run, dst, and set current
day/time.
(In all cases, the
combination to enter the
Installer Setup and the
Installer Test is
available.)
4 to 10
Heating and cooling
setpoints can be set no
closer than the chosen
value between 3° F and
10 °F (1.5 and 5 °C).
0, 1, 2, 3,
Choose 0, 1, 2, 3, 4 or 5
4 or 5
minute minimum off time
for the compressor.
40°F
Maximum setpoint range
through
stop can be set
90°F
anywhere between 40° F
(4.5°C to
and 90°F in 1°F (0.5°C)
32°C).
increments.
45°F
Minimum setpoint range
through
stop can be set
99°F (7°C
anywhere between 45°F
to 37°C).
and 99°F in 1°F (0.5°C.)
increments.
or
69-1331—5