DELTANET FS90 OPERATING INSTRUCTIONS
Switch/
LED
Micro-
Resets microprocessor.
Processor
Reset Switch
Acknowledge
Acknowledges troubles and alarms or silences outputs as follows:
/Silence
Acknowledge position (UP): The local audible silences and blinking LEDs change to
Switch
steady on. The Acknowledge/Silence switch does not affect indicating zone outputs or
silence alarm signals.
NOTE: Zones set up as central are acknowledged when the new status reports to
the central processor. FS90 acknowledgement of these zones is not required
unless communication with the central fails and stand-alone mode is in effect.
Silence position (DOWN): The indicating zone devices silence, the FS90 local audible
silences, the CA Board Silence LED turns on and blinking LEDs change to steady on.
NOTE: Operators may also silence zones set up as central from the central
processor.
Reset Switch Resets FS90. The system removes power to all initiating zones for 15 seconds,
activates the CA Board reset out signal for 15 seconds and returns all input zone status
indicators and their associated outputs to normal. After the 15-second reset time any
zone(s) remaining in alarm or trouble annunciates as a new alarm or trouble.
Panel Test
Initiates a test of all LEDs except the communication board transmit and receive LEDs.
Switch
The test turns on the LEDs and sounds the local audible. The test indicates that all
function boards are operational and controlled by the CA Board microprocessor. The
panel test does not affect alarm or trouble reporting in the system.
Manual
Initiates a manual evacuation signal. All indicating zones turn on and a common alarm
Evacuation
indication and pulsing local audible occur (if audible is selected and the system is in the
Switch
stand-alone mode). Toggle the Acknowledge/Silence switch to silence the output and
then toggle the Reset switch to return the system to normal.
Setup Switch Enters Setup Mode.
Alarm LED
Indicates a common alarm in the system via blinking LED.
Trouble LED
Indicates a common trouble via a blinking yellow LED.
Silence LED
Indicates the Silence switch has been activated to silence the outputs.
Low Battery
Indicates a low battery condition if system power supply is off. If a Battery Supervision
LED
Module is installed, this LED indicates low battery or absence of batteries at all times.
Ground Fault
Indicates a ground fault in the system.
LED
Isolate LED
Indicates one of the Disconnect switches on a module is activated or a point has been
isolated or locked out.
Power LED
Indicates power is on.
Run LED
Indicates system is ready to operate.
Setup LED
Off
MAINTENANCE PROCEDURES
The system must be maintained in accordance with the system
documentation and procedures and practices contained in applicable
NFPA and UL standards, including NFPA 70, 72, 90A, 92A and 92B.
DeltaNet FS90 Systems Maintenance and Repair Manual for further
details, including testing, fuse replacement and replacement parts.
For service, contact your local Honeywell Automation & Control
Solutions office as listed in the phone book, or contact a regional
office as shown at the end of this document.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
www.honeywell.com/buildingsolutions
® U.S. Registered Trademark
© 2007 Honeywell International Inc.
74-5069
J.I.
11-07
Table 1. CA Board Switch and LED Functions.
Normal Operation
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
Exits Setup Mode. Any changes made
during Setup Mode will be lost if this
switch is activated.
Advances pointer to next function.
Selects or deselects characteristics.
Enter characteristics into date file and
moves pointer.
Not used.
Exits Setup Mode.
Indicates the system is ready to enter
group address menu.
Indicates the system is ready to enter
code menu.
Indicates the system is ready to enter
the special options menu.
Indicates various time menus when
used with ground fault and disconnect
LEDs.
Indicates various time menus when
used with low battery and disconnect
LEDs.
Indicates various time menus when
used with low battery and ground fault.
Indicates system is ready to enter
output menu.
Indicates system is ready to enter input
menu.
On to show system is in Setup Mode.
This product may contain small amounts of chemicals
and substances that may be banned from disposal in
landfills. At the end of the useful life of this product, it is
the owners' responsibility to safely decommission the
product and arrange for disposal in accordance with all
applicable environmental laws and regulations, including
Directive 2002/96/EC of the European parliament and the Council of
27 January 2003 on Waste Electrical and Electronic Equipment
(WEEE).
Setup Mode

Advertisement

loading