Lockout Modes; Valve-On Delays/Blower Motor- Off Delays; Specifications; Installation - Honeywell R7284B Installation Instructions Manual

Electronic oil primary, enviracom enabled
Hide thumbs Also See for R7284B:
Table of Contents

Advertisement

Available languages

Available languages

R7284B,P,U,G ELECTRONIC OIL PRIMARY, ENVIRACOM™ ENABLED

Lockout Modes

The R7284 has three types of lockout modes that are
entered when an error is encountered:
• Soft Lockout: Caused by a temporary internal error
such as low voltage. The control recovers
automatically after the error is no longer detected.
• Hard Lockout: Caused by a failure internal to the
control or by a system fault such as flame out of
sequence. A Hard Lockout will result in a no heat
condition. To reset from Hard Lockout press and
hold the "i" button for 2 seconds.
• Restricted Lockout: Caused by a number of
consecutive hard lockouts on the same heat cycle.
To reset from a Restricted Lockout press and hold
the "i" button for ten seconds.
Valve-on Delays/Blower Motor-
off Delays
Select models may have fixed or adjustable delays for
valve open or blower motor off. The safety circuits will
check for flame during these delays and, if a flame is
present, will switch the control to lockout.

SPECIFICATIONS

Models:
Table 1 lists the major features for the R7284.
Timing:
Valve-on Delay: 0–30 seconds
Burner Off Delay: 0–8 minutes
Lockout: 15, 30 or 45 seconds.
Recycle: 60 seconds (fixed).
Ignition Carryover: 10 seconds (fixed).
NOTE: Some models have adjustable Valve-on Delay,
Burner Off Delay, and Lockout timings.
Model
Limit
R7284B
No
R7284G
No
R7284P
Yes
R7284U
Yes

INSTALLATION

When Installing This Product...
1. Read these instructions carefully. Failure to fol-
low instructions can damage the product or
cause a hazardous condition.
2. Check ratings given in these instructions and on
the product to make sure the product is suitable
for your application.
3. Make sure the installer is a trained, experienced
service technician.
4. Use these instructions to check out the product
operation after installation.
69-2467EFS—09
Table 1. R7284 Models.
Valve
Yes
Valve on delay only
No
No on/off delays, intermittent ignition (wire igniter together with motor)
Yes
Valve on and valve off delays
Yes
Valve on and valve off delays
Electrical Ratings:
Inputs:
Voltage: 102 to 132 Vac, 120 Vac nominal.
Current: 0.5A plus burner motor, valve and igniter
loads.
Frequency: 60 Hz.
Outputs:
Relay Contacts:
Burner: 120 Vac, 10 full load amperes (FLA), 60
locked rotor amperes (LRA).
Valve: 120 Vac, 1A.
Igniter: 120 Vac, 3 A.
Low Voltage Shutdown: 80 Vac
Thermostat Current Available: 100 mA.
EnviraCOM™ Current Available: 150 mA.
NOTE: Reduce burner FLA rating by igniter load. For
example, if the igniter draws 3A (120 Vac, 360
VA), reduce the burner motor FLA to 7A.
Typical Component Wire Color Code:
White: Neutral.
Black: Line.
Orange: Motor.
Blue or Blue w/White Stripe: Igniter.
Violet: Valve.
Red: Limit.
NOTE: The R7284 is provided with 1/4" quick-con-
nect terminals.
Environmental Ratings:
Operating/Shipping Temperature: -40°F to +150°F
(-40°C to +66°C).
Display text may not be visible below -4°F (-20°C)
Humidity: 0% to 95% relative humidity at 104°F
(40°C), noncondensing.
Accessories:
W8735S3000 Alarm Module
Approvals:
Underwriters Laboratories Inc.: Recognized (File
MP268).
Canadian Underwriters Laboratories Inc.
Notes
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning
installation to prevent electrical shock or
equipment damage. More than one disconnect
may be involved.
2