Honeywell NXS0003V35A2H1 Product Data page 9

Nxs series
Table of Contents

Advertisement

Reference output (voltage for
1
+10 V
ref
potentiometer etc.)
2
AI1 +
Analogue Input 1 (V signal)
3
AI1 –
I/O ground
4
AI2 +
Analogue Input 2 (mA signal)
5
AI2 –
Analogue Input 2 (mA signal)
6
+24 V
+24 V input/output (max. 0.1 A)
7
GND
I/O ground
8
DIN1
Digital Input 1
9
DIN2
Digital Input 2
10 DIN3
Digital Input 3
Digital input common for DIN1,
11 CMA
DIN2, and DIN3
12 +24 V
Same as terminal 6
13 GND
I/O ground
14 DIN4
Digital Input 4
15 DIN5
Digital Input 5
16 DIN6
Digital Input 6
Digital input common for DIN4,
17 CMB
DIN5, and DIN6
18 AO1 +
Analogue output 1, default range:
0–20 mA/R
19 AO1 –
20 DO1
Open collector Output
Fig. 7. NXS control connections
, max. 500 Ω
L
NXS VARIABLE FREQUENCY DRIVES
21 RO1
22 RO1
23 RO1
25 RO2
26 RO2
28 TI+
Thermistor Input;
Rtrip = 4.7 kΩ (PTC)
29 TI-
9
Relay 1
NO/NC
Relay 2
NO
EN0B-0620GE51 R1107