A.1 Technical Specifications
Table A-1 Technical Specifications
Category
Environmental
conditions
AC input
DC output
Issue 06 (2014-02-20)
Item
Operating
temperature
Transportation
temperature
Storage
temperature
Operating
humidity
Storage humidity
Altitude
Input mode
Input voltage
Input frequency
Power factor
Output voltage
range
Default output
voltage
Maximum output
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
A
Specifications
-40º C to +70º C
NOTE
The system can run for 8 hours at 70º C.
-40º C to +70º C
-40º C to +70º C
5%-95%
5%-95%
0-4000 m
When the altitude ranges from 2000 m to 4000 m,
the operating temperature decreases by 1º C for each
additional 200 m.
Single-phase three-wire (L, N, PE)
85–300 V AC (rated voltage: 220 V AC)
45–66 Hz (rated frequency: 50/60 Hz)
≥ 0.99 (100% load)
-42 V DC- -58 V DC
-53.5 V DC
2000 W