7.2.13 Batt Off

Possible Causes
Measures
1.
2.
3.
4.
5.

7.2.14 Door Alarm

Possible Causes
Measures
1.
2.
Issue 06 (2014-02-20)
The contactor is faulty.
Check whether the battery circuit breaker trips or battery fuse detection cable is
disconnected. If yes, reconnect the cable.
Check whether the battery circuit breaker trips or battery fuse is blown. If yes, rectify the
battery loop fault and then switch on the circuit breaker or replace the fuse.
Manually switch on or switch off the battery contactor and check the battery current
changes accordingly. If no, replace the contactor.
An AC power failure occurs.
Batteries are manually disconnected.
The battery disconnection voltage is set too high on the SMU.
Rectifiers are faulty.
The system configuration is not proper.
Check whether an AC power failure occurs. If yes, resume the AC power supply.
Check whether batteries are manually disconnected. If yes, confirm the reason of the
manual disconnection, and reconnect the batteries after the operation.
Check whether the battery disconnection voltage (43 V DC by default)is set too high on
the SMU. If yes, adjust it to a proper value.
Check whether the power system capacity is insufficient for the loads due to rectifier
failures. If yes, replace the faulty rectifier.
Check whether the load current is greater than the current power system capacity. If yes,
expand the power system capacity or reduce the load power.
This alarm is generated only for the power system that has door status sensor installed.
The cabinet doors are open.
The door status sensor is faulty.
Close cabinet doors.
Check whether the door status sensor is faulty. If yes, replace the door status sensor.