ABB COM600S User Manual page 55

Com600 series, modbus tcp master, opc
Hide thumbs Also See for COM600S:
Table of Contents

Advertisement

1MRS756445
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Table 3.4.8.11-1 Configurable INC properties for OPC servers with Modbus device,
subtype REGISTER_BASED_CONTROL
Property/Para-
Value or Value range/ Default
meter
/Example
Basic
61850-Type
INC
Subtype
REGISTER_BASED_CON-
TROL
Addresses
Control Register
0 - 65535
Default: 0
Format
Default
Word
Integer
Long MSW first
Long MSW last
Float MSW first
Float MSW last
Bit
Default: Word
Indication Register
0 - 65535
Default: 0
Scale and Unit
Indication Scale
Default: None
Table 3.4.8.11-2 Configurable INC properties for OPC servers with Modbus device,
subtype DPU_REGISTER_BASED_CONTROL
Property/Para-
Value or Value range/ Default
meter
/Example
Basic
61850-Type
INC
Subtype
DPU_REGISTER_BASED_CON-
TROL
Addresses
Description
61850-Type
Holding register address for the control.
Holding register (4X reference) address
range 40001 - 49999 . Address 0 equals
to no information available.
Data format of the control and the indica-
tion.
Holding or input register address for the
indication. Holding register (4X reference)
address range 40001 - 49999 or input
register (3X reference) address range
30001 - 39999 . Address 0 equals to no
information available.
Scale to be used with the indication value.
Description
61850-Type
55