1MRS756445
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Property/Para-
Value or Value range/ Default
meter
/Example
Address For Status
0 to 65535
Default
Bit Mask for Fail
0 to 65535
Alarm
Default
Bit Mask for Inverse
0 to 65535
status
Default
Bit Mask for status
0 to 65535
Default
Table 3.4.8.8-3 Configurable DPC properties for OPC servers with Modbus device,
subtype BIT_DPU_SBO/ BIT_DPU_MCD_SBO
Property/Para-
Value or Value range/ Default
meter
/Example
Basic
61850-Type
DPC
Subtype
BIT_DPU_SBO
BIT_DPU_MCD_SBO
Addresses
Address For Control
0 to 65535
Register
Default: 0
Address For Con-
0 to 65535
firm Register
Default: 0
Address For
0 to 65535
Execute Register
Default: 0
Open command
0 to 65535
value
Default: 0
Close command
0 to 65535
value
Default: 0
Description
Coil/Input/Holding register address. Coil
= 0x reference address range 1 to 9999
Or input = 1x reference address range
10001 to 19999 Or holding register = 4x
reference range 40001 to 49999 or Input
register = 3x reference address range
30001 to 39999. Address 0 equals to no
information available (0 to 65535)
Bit mask for fail alarm
Bit mask for inverse status
Bit mask for status
Description
61850-Type
Holding address for the Vendor name.
Holding register = 4x reference address
range 40001 to 49999. Address 0 equals
to no information available.
Holding address for the Vendor name.
Holding register = 4x reference address
range 40001 to 49999. Address 0 equals
to no information available.
Holding address for the Vendor name.
Holding register = 4x reference address
range 40001 to 49999. Address 0 equals
to no information available.
Open command type
Close command type
47